New techniques to speed up voltage collapse computations using tangent vectors

被引:117
作者
deSouza, ACZ [1 ]
Canizares, CA [1 ]
Quintana, VH [1 ]
机构
[1] UNIV WATERLOO,DEPT ELECT & COMP ENGN,WATERLOO,ON N2L 3G1,CANADA
关键词
network partitioning; voltage stability index; voltage collapse; continuation power flows; on-line security analysis;
D O I
10.1109/59.630485
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper discusses various methods based on network partitioning and voltage stability indices to accelerate the computation of voltage collapse points using continuation techniques. Partitioning methods derived from right eigenvector and tangent vector information are thoroughly studied, identifying limitations and probable a mixed partition-reduction technique is then proposed to reduce computational burden. Also, tangent vectors are used to define a clustering method for the identification at any operating condition of the critical area at the collapse point, and. a new voltage stability index is defined based on the identification of this critical area. Finally, a predictor-corrector methodology based on this index and the continuation method is proposed for fast computations of voltage collapse points. All the different methods are compared based on the results obtained for the IEEE 300-bus test system, and a methodology is recommended based on its prospective computational savings.
引用
收藏
页码:1380 / 1387
页数:8
相关论文
共 27 条
[1]   THE CONTINUATION POWER FLOW - A TOOL FOR STEADY-STATE VOLTAGE STABILITY ANALYSIS [J].
AJJARAPU, V ;
CHRISTY, C .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1992, 7 (01) :416-423
[2]   AN ALGORITHM FOR PARTITIONING THE NODES OF A GRAPH [J].
BARNES, ER .
SIAM JOURNAL ON ALGEBRAIC AND DISCRETE METHODS, 1982, 3 (04) :541-550
[3]  
BARQUIN J, 1995, IEEE PES 95 WM 1834
[4]   POINT OF COLLAPSE METHODS APPLIED TO AC DC POWER-SYSTEMS [J].
CANIZARES, CA ;
ALVARADO, FL ;
DEMARCO, CL ;
DOBSON, I ;
LONG, WF ;
PAL, MK ;
SEMLYEN, A .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1992, 7 (02) :673-683
[5]   CONDITIONS FOR SADDLE-NODE BIFURCATIONS IN AC/DC POWER-SYSTEMS [J].
CANIZARES, CA .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 1995, 17 (01) :61-68
[6]   POINT OF COLLAPSE AND CONTINUATION METHODS FOR LARGE AC DC SYSTEMS [J].
CANIZARES, CA ;
ALVARADO, FL .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1993, 8 (01) :1-8
[7]   ON BIFURCATIONS, VOLTAGE COLLAPSE AND LOAD MODELING [J].
CANIZARES, CA .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1995, 10 (01) :512-522
[8]  
CANIZARES CA, 1995, IEEE PES 95 SM 5835
[9]  
*CIGRE, 1993, 380210 CIGRE
[10]   NEW TECHNIQUE OF NETWORK PARTITIONING FOR VOLTAGE COLLAPSE MARGIN CALCULATIONS [J].
DESOUZA, ACZ ;
QUINTANA, VH .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 1994, 141 (06) :630-636