Experimental Verification of Distribution Transformer Model under Lightning Strokes

被引:0
作者
Sabiha, Nehmdoh A. [1 ]
Lehtonen, Matti [1 ]
机构
[1] Helsinki Univ Technol TKK, Fac Elect Commun & Automat, Dept Elect Engn, Power Syst & High Voltage Lab, Helsinki, Finland
来源
2009 IEEE/PES POWER SYSTEMS CONFERENCE AND EXPOSITION, VOLS 1-3 | 2009年
关键词
distribution transformer; lightning strokes; high frequency transformer model; ATP/EMTP;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In this paper, the distribution transformer model under lightning impulses introduced by Piantini at no load conditions is investigated. This model is modified where this modification takes more than one resonance frequency into consideration during the model parameters calculation. Therefore, the frequency response of the simulated transient voltage is improved comparing with Piantini model. The verification of the modified model is carried out through the comparison between the experimental and simulation results, in which the time domain simulation is carried out using ATP/EMTP while MATLAB is used to identify the model parameters. The comparison showed a good agreement between the simulation and experimental results.
引用
收藏
页码:2011 / 2016
页数:6
相关论文
共 14 条
[1]  
BACHEGA RJ, 2004, IEEE PES TRANSM DIST
[2]  
DUGAN RC, 1996, ELECT POWER SYSTEMS
[3]  
Kanashiro A. G., 2002, INT C GROUND EARTH 3
[4]  
KANASHIRO AG, 2001, P 6 INT S LIGHTN PRO, P275
[5]  
Noda T., 2002, IEEE T POWER DELIVER, V17
[6]  
NODA T, 2004, IEEE T POWER DELIVER, V19
[7]  
Okabe S., 1997, Transactions of the Institute of Electrical Engineers of Japan, Part B, V117-B, P700
[8]  
OKABE S, 2001, ELECT ENG JAPAN, V134
[9]  
PIANTINI A, 1999, IEEE 5 INT S LIGHT P
[10]  
PIANTINI A, 1999, CIRED INT C EL DISTR