Partial Discharges Pulse Shape Analysis at AC and DC

被引:0
作者
Pihera, Josef [1 ]
Hornak, Jaroslav [1 ]
Vobornik, Ales [1 ]
Kupka, Lukas [1 ]
Chladek, Svatoslav [1 ]
Haller, Rainer [1 ]
机构
[1] Univ West Bohemia, Fac Elect Engn, Reg Innovat Ctr Elect Engn, Plzen, Czech Republic
来源
PROCEEDINGS OF THE 21ST INTERNATIONAL SYMPOSIUM ON HIGH VOLTAGE ENGINEERING, VOL 1 | 2020年 / 598卷
关键词
Partial discharges; Pulse shape; Measuring impedance; Statistical analysis;
D O I
10.1007/978-3-030-31676-1_52
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Partial discharge (PD) signal analysis is a well-known tool for monitoring the conditions of insulation systems of electrical machines and equipment. Classical analyzes of PD are mostly based on the evaluation of the phase angle of the test voltage at which partial discharges occur. At the present, the partial discharge detection is mostly based on the measurement of charging currents that are needed to resume the voltage on the sample that was there before the partial discharge occurred. Other electrical methods are, for example, the scanning of an electromagnetic field emitted during a partial discharge. Another developed methodology in the field of measuring and analyzing partial discharges is the monitoring of pulse parameters of the detected discharge. Experiments suggest that measuring the rise and fall time of the pulse edges and amplitude measurements can evaluate the partial discharge signal. Especially this method could be very helpful at the moment when partial discharges at DC are studied and evaluated. The disadvantage of partial discharges at DC is the fact there is no phase and phase angle position for PD patterns recognition. Thus, another evaluation method development is necessary for PD recognition DC. There is presented in the study an experiment where the PD pulse shapes, in the manner of rise time and fall time, were investigated at laboratory PD models at both voltage types AC and DC. The PD models simulated corona discharges. Each individual pulse of a partial discharge can be detected by a suitable scanning impedance and viewed with fast digital oscilloscopes. As has been said, there is a presumption that different discharge arrangements or even variously degraded insulating materials have different waveforms of the sensed pulses. The main monitored parameters of individual pulses are their rise time and amplitude. Since the occurrence of partial discharge is essentially a random phenomenon, statistical analysis of a significant amount of data is required. A view of the behaviour of the partial discharge pulse in various cases of the discharge activity brings different results in the observation of the pulse rise time and its amplitude in the various observed setups. Monitoring the rise time and pulse amplitude is one way of evaluating partial discharges, regardless of their superimposed position on the sine wave of the supply voltage. Thus this PD monitoring could be a part of PD evaluation at DC. These pulse parameters together with other PD analysis at DC (as pulse sequence analysis) could be used to estimate the partial discharge type as well as to evaluate the deterioration of the insulation of electrical machines.
引用
收藏
页码:549 / 559
页数:11
相关论文
共 50 条
  • [31] Investigating Conditions for an Unexpected Additional Source of Partial Discharges in DC Cables: Load Power Variations
    Naderiallaf, Hadi
    Seri, Paolo
    Montanari, Gian Carlo
    IEEE TRANSACTIONS ON POWER DELIVERY, 2021, 36 (05) : 3082 - 3090
  • [32] Characterization of Partial Discharges in Solid Insulators under DC Voltage Using Physical Cavity Properties
    Morette, Nathalie
    Daassi-Gnaba, Hela
    Ditchi, Thierry
    Oussar, Yacine
    2017 INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATING MATERIALS (ISEIM), VOLS 1 & 2, 2017, : 374 - 377
  • [33] Effect of Cellulose Impurities on Partial Discharges in Oil-pressboard Insulation under DC Voltage
    Li, Yuan
    Zhang, Qiaogen
    Ding, Yuqin
    Zhao, Yi
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2017, 24 (04) : 2271 - 2273
  • [34] Thermodynamic analysis of the degradation of polyethylene subjected to internal partial discharges
    Leon-Garzon, Andres R.
    Dotelli, Giovanni
    Villa, Andrea
    Barbieri, Luca
    Gondola, Marco
    Cavallotti, Carlo
    CHEMICAL ENGINEERING SCIENCE, 2018, 180 : 1 - 10
  • [35] SEPARATION OF PARTIAL DISCHARGES FROM PULSE-SHAPED NOISE SIGNALS WITH THE HELP OF NEURAL NETWORKS
    BORSI, H
    GOCKENBACH, E
    WENZEL, D
    IEE PROCEEDINGS-SCIENCE MEASUREMENT AND TECHNOLOGY, 1995, 142 (01) : 69 - 74
  • [36] Analysis of Partial Discharges in Electrical Tree Growth Under Very Low Frequency (VLF) Excitation Through Pulse Sequence and Nonlinear Time Series Analysis
    Donoso, Pablo
    Schurch, Roger
    Ardila, Jorge
    Orellana, Luis
    IEEE ACCESS, 2020, 8 : 163673 - 163684
  • [37] UHF Technique for Identification of Partial Discharge in a Composite Insulation Under AC and DC voltages
    Sarathi, R.
    Koperundevi, G.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2008, 15 (06) : 1724 - 1730
  • [38] Degradation Characteristics of Oil-immersed Pressboard Samples Induced by Partial Discharges under DC Voltage
    Li, Yuan
    Zhang, Qiaogen
    Wang, Tonglei
    Li, Jinzhong
    Guo, Can
    Ni, Heli
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2017, 24 (02) : 1110 - 1117
  • [39] Measuring partial discharges in MV cables under DC voltage: procedures and results in steady state conditions
    Naderiallaf, Hadi
    Cavallini, Andrea
    Esterl, Florian
    Plath, Ronald
    Seri, Paolo
    Montanari, Gian Carlo
    2020 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), 2020, : 18 - 21
  • [40] Modified Pulse Sequence Analysis for PD measurement at DC
    Pihera, Josef
    Hornak, Jaroslav
    Kupka, Lukas
    Mullerova, Eva
    Haller, Rainer
    2018 IEEE 2ND INTERNATIONAL CONFERENCE ON DIELECTRICS (ICD), 2018,