Evaporative Cooling of Water in a Rotating Packed Bed (Split Packing)

被引:11
作者
Bhattacharya, S. [1 ]
Mondal, A. [1 ]
Bhowal, A. [1 ]
Datta, S. [1 ]
机构
[1] Jadavpur Univ, Dept Chem Engn, Kolkata 700032, India
关键词
PROCESS INTENSIFICATION; CARBON-DIOXIDE; MASS-TRANSFER; TOWER; FLOW; ABSORPTION; HIGEE; DISTILLATION; PERFORMANCE; CONTACTOR;
D O I
10.1021/ie901207m
中图分类号
TQ [化学工业];
学科分类号
0817 ;
摘要
Rotating packed beds (RPB) have been Studied for intensifying mass-transfer processes. This work was undertaken to evaluate the thermal performance of in RPB with split packing for evaporative cooling of water involving simultaneous heat and mass transfer. Higher efficiency was achieved within a smaller contactor volume compared to mechanical draft cooling towers. At all values of the liquid-to-air flow rate ratio studied, efficiency was not significantly affected by rotor speed and decreased with increasing rotor speed beyond a certain limit at low air and water flow rates. A simple mathematical model was used to estimate process parameters from the experimental data based oil the Merkel assumption. The h(G)a/k(Y)aC(s) ratio varied between 0.85 and 1.18, and the tower characteristic of the RPB was between 1.4 and 4.0.
引用
收藏
页码:847 / 851
页数:5
相关论文
共 27 条
[1]   Experimental investigation of the performance of a counter-flow, packed-bed mechanical cooling tower [J].
Bedekar, SV ;
Nithiarasu, P ;
Seetharamu, KN .
ENERGY, 1998, 23 (11) :943-947
[2]   Characteristics of flow in a rotating packed bed (HIGEE) with split packing [J].
Chandra, A ;
Goswami, PS ;
Rao, DP .
INDUSTRIAL & ENGINEERING CHEMISTRY RESEARCH, 2005, 44 (11) :4051-4060
[3]   Volatile organic compounds absorption in a cross-flow rotating packed bed [J].
Chen, Yu-Shao ;
Hsu, Yi-Chun ;
Lin, Chia-Chang ;
Tai, Clifford Yi-Der ;
Liu, Hwai-Shen .
ENVIRONMENTAL SCIENCE & TECHNOLOGY, 2008, 42 (07) :2631-2636
[4]   Experimental study and predictions of an induced draft ceramic tile packing cooling tower [J].
Elsarrag, Esam .
ENERGY CONVERSION AND MANAGEMENT, 2006, 47 (15-16) :2034-2043
[5]  
FOUST AS, 1994, PRINCIPLES UNIT OPER
[6]   Experimental study on the performance of mechanical cooling tower with two types of film packing [J].
Gharagheizi, Farhad ;
Hayati, Reza ;
Fatemi, Shohreh .
ENERGY CONVERSION AND MANAGEMENT, 2007, 48 (01) :277-280
[7]   The investigation of cooling tower packing in various arrangements [J].
Goshayshi, HR ;
Missenden, JF .
APPLIED THERMAL ENGINEERING, 2000, 20 (01) :69-80
[8]  
HENSEL SL, 1952, CHEM ENG PROG, V48, P362
[9]   Distillation studies in a high-gravity contactor [J].
Kelleher, T ;
Fair, JR .
INDUSTRIAL & ENGINEERING CHEMISTRY RESEARCH, 1996, 35 (12) :4646-4655
[10]  
KEYVANI M, 1989, CHEM ENG PROG, V85, P48