Integrated CO2 systems for supermarkets: Field measurements and assessment for alternative solutions in hot climate

被引:25
作者
Azzolin, Marco [1 ]
Cattelan, Gianluca [1 ]
Dugaria, Simone [2 ]
Minetto, Silvia [3 ]
Calabrese, Livio [4 ]
Del Col, Davide [1 ]
机构
[1] Univ Padua, Dept Ind Engn, Via Venezia 1, I-35131 Padua, Italy
[2] Free Univ Bolzano Bozen, Fac Sci & Technol, Piazza Univ 5, I-39100 Bolzano, Italy
[3] Natl Res Council Italy, Construct Technol Inst, Corso Stati Uniti 4, I-35127 Padua, Italy
[4] Frascold SpA, Via Barbara Melzi 103, I-20027 Rescaldina, MI, Italy
关键词
Carbon dioxide; Commercial refrigeration; Transcritical booster system; Overfed evaporators; Vapour ejector; Evaporative gas cooler; REFRIGERATION SYSTEMS; THERMODYNAMIC ANALYSIS; ENERGY; PLANT;
D O I
10.1016/j.applthermaleng.2021.116560
中图分类号
O414.1 [热力学];
学科分类号
摘要
In Europe CO2 transcritical booster systems have become a trusted solution in the field of commercial refrigeration. The main challenge for these systems is to become appealing in warm climates. Beside the various technological solutions that can be introduced, an interesting possibility is to fulfill all the thermal needs (refrigeration, heating and air-conditioning) with one single and compact unit. The present paper focuses on the monitoring of an integrated CO2 transcritical booster system, serving a 1500 m(2) supermarket located in Italy, able to satisfy both cooling and heating demands using one single unit. The analysis of the monitoring data shows that the unit performance is strongly influenced by the high gas cooler discharge temperature in the summer and by the implemented control strategy for heat recovery. While the parallel compression can increase the system capacity and also entirely satisfy the air-conditioning demand, the system efficiency is still strongly penalized at high external temperatures. In wintertime, the system is forced to work in transcritical condition and the use of the external evaporator allows to entirely meet the space heating and sanitary hot water demands of the supermarket. A steady-state model of the considered refrigeration system is developed and validated against the collected field measurements. The model is then used to assess some solutions to improve the performance of the integrated CO2 booster unit. The simulated configurations considered overfed evaporators, vapour ejectors and evaporative gas cooler. To face the challenge of improving the performance of CO2 system in warm climates, simulations have been run for the cities of Milan and Tunis. The results of the simulations show that vapour ejectors and evaporative gas cooler offer a good potential to reduce the electrical power consumption during the warmest periods, while overfed evaporators increase the performance almost independently from the external temperature. The combined adoption of overfed evaporators along with ejectors and evaporative gas cooler can increase up to 18% the yearly average COP in both locations compared to the original booster system configuration. For existing systems the adoption of overfed freezers and evaporative gas cooler along with the increase of the evaporating pressure at the external evaporator are considered as possible solutions to increase the performance with limited changes.
引用
收藏
页数:19
相关论文
共 32 条
[1]  
Abdi A, 2014, 11TH IIR GUSTAV LORENTZEN CONFERENCE ON NATURAL REFRIGERANTS (2014), P277
[2]  
[Anonymous], 2013, 129002013 REFRIGERAN
[3]   Transcritical CO2 commercial refrigeration plant with adiabatic gas cooler and subcooling via HVAC: Field tests and modelling [J].
Cortella, G. ;
D'Agaro, P. ;
Coppola, M. A. .
INTERNATIONAL JOURNAL OF REFRIGERATION, 2020, 111 :71-80
[4]   Effect of dedicated mechanical subcooler size and gas cooler pressure control on transcritical CO2 booster systems [J].
D'Agaro, P. ;
Coppola, M. A. ;
Cortella, G. .
APPLIED THERMAL ENGINEERING, 2021, 182
[5]   Field tests, model validation and performance of a CO2 commercial refrigeration plant integrated with HVAC system [J].
D'Agaro, R. ;
Coppola, M. A. ;
Cortella, G. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 100 :380-391
[6]   Review of carbon dioxide (CO2) based heating and cooling technologies: Past, present, and future outlook [J].
Dilshad, Saad ;
Kalair, Ali Raza ;
Khan, Nasrullah .
INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2020, 44 (03) :1408-1463
[7]   Thermodynamic analysis of a transcritical CO2/propylene (R744-R1270) cascade system for cooling and heating applications [J].
Dubey, Alok Manas ;
Kumar, Suresh ;
Das Agrawal, Ghanshyam .
ENERGY CONVERSION AND MANAGEMENT, 2014, 86 :774-783
[8]  
Dugaria S, 2019, CONGRES INT FROID, P3509, DOI 10.18462/iir.icr.2019.1154
[9]   ENERGY ANALYSIS OF CO2 REFRIGERATION SYSTEMS USING MEASURED VALUES OF COMPRESSOR EFFICIENCY [J].
Dugaria, Simone ;
Calabrese, Livio ;
Azzolin, Marco ;
Minetto, Silvia ;
Del Col, Davide .
13TH IIR GUSTAV LORENTZEN CONFERENCE ON NATURAL REFRIGERANTS: NATURAL REFRIGERANT SOLUTIONS FOR WARM CLIMATE COUNTRIES, 2018, :1138-1146
[10]  
Foslie S., 2020, 6 IIR C SUST COLD CH