Indoor humidity behaviors associated with decoupled cooling in hot and humid climates

被引:136
作者
Zhang, LZ [1 ]
Niu, JL [1 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Kowloon, Hong Kong, Peoples R China
关键词
air-conditioning; radiant cooling; humidity; building simulation;
D O I
10.1016/S0360-1323(02)00018-5
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Radiant cooling with independent air dehumidification/ventilation is a complementary cooling and ventilation technology that has the potential to provide better thermal comfort, air quality and energy consumption than conventional all-air systems. However, in hot and humid regions, fears for the risk of condensation on ceiling panels limit its market penetration. To address this problem, in this paper, indoor humidity behaviors associated with decoupled cooling in hot and humid climates are investigated. Room mean temperature, mean humidity, maximum RH on the ceiling panel surfaces, annual condensation hours and annual primary energy consumptions are predicted with systems combining chilled ceiling with various air dehumidification and ventilation strategies, using a building energy simulation code ACCURACY. The effects of night air infiltration rates and the ratios of air flow rates of return air to those of fresh air on the indoor humidity performance and annual condensation hours are discussed. The results indicate that dehumidification and ventilation prior to cooling panels operation is required to reduce condensation risks in hot and humid climates. It is also revealed that a I h in advance dehumidification/ventilation in summer could completely eliminate the condensation problems. (C) 2002 Elsevier Science Ltd. All rights reserved.
引用
收藏
页码:99 / 107
页数:9
相关论文
共 21 条
[1]  
American Society of Heating Refrigerating and Air-Conditioning Engineers, 1999, 621999 ANSIASHRAE
[2]  
[Anonymous], 1998, ASHRAE T
[3]  
[Anonymous], BUILD ENV
[4]  
[Anonymous], 1988, ASHRAE Transactions
[5]  
*ASHRAE, 1997, 1997 ASHRAE HDB FUND
[6]  
Brodrick JR, 2001, ASHRAE J, V43, P58
[7]   HYDRONIC RADIANT COOLING - PRELIMINARY ASSESSMENT [J].
FEUSTEL, HE ;
STETIU, C .
ENERGY AND BUILDINGS, 1995, 22 (03) :193-205
[8]   Thermal comfort and energy consumption of the radiant ceiling panel system. Comparison with the conventional all-air system [J].
Imanari, T ;
Omori, T ;
Bogaki, K .
ENERGY AND BUILDINGS, 1999, 30 (02) :167-175
[9]  
JURINAK JJ, 1983, P ASME SOL EN DIV 5, P374
[10]  
Kittler R, 1996, ASHRAE TRAN, V102, P613