Effects of dissolved air on subcooled flow boiling of a dielectric coolant in a microchannel heat sink

被引:53
作者
Chen, Tailian [1 ]
Garimella, Suresh V. [1 ]
机构
[1] Purdue Univ, Sch Mech Engn, Cooling Technol Res Ctr, W Lafayette, IN 47907 USA
关键词
D O I
10.1115/1.2351905
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The effects of dissolved air in the dielectric liquid FC-77 on flow boiling in a microchannel nel heat sink containing ten parallel channels, each 500 mu m wide and 2.5 mm deep, were experimentally investigated. Experiments were conducted before and after degassing, at three flow rates in the range of 30-50 ml/min. The dissolved air resulted in a significant reduction in wall temperature at which bubbles were first observed in the microchannels. Analysis of the results suggests that the bubbles observed initially in the undegassed liquid were most likely air bubbles. Once the boiling process is initiated, the wall temperature continues to increase,for the undegassed liquid, whereas it remains relatively unchanged in the case of the degassed liquid. Prior to the inception of boiling in the degassed liquid, the heat transfer coefficients with the undegassed liquid were 300 similar to 500% higher than for degassed liquid, depending on the flow rate. The heat transfer coefficients for both cases reach similar values at high heat fluxes (> 120 kW/m(2)) once the boiling process with the degassed liquid was well established. The boiling process induced a significant increase in pressure drop relative to single-phase flow; the pressure drop for undegassed liquid was measured to be higher than for degassed liquid once the boiling process became well established in both cases. Flow instabilities were induced by the boiling process, and the magnitude of the instability was quantified using the standard deviation of the measured pressure drop at a given heat flux. It was found that the magnitude of flow instability increased with increasing heat flux in both the undegassed and degassed liquids, with greater flow instability noted in the undegassed liquid.
引用
收藏
页码:398 / 404
页数:7
相关论文
共 13 条
[1]  
*3M, 1995, 3M FLUOR LIQ PROD MA
[2]   CORRELATION FOR BOILING HEAT TRANSFER TO SATURATED FLUIDS IN CONVECTIVE FLOW [J].
CHEN, JC .
INDUSTRIAL & ENGINEERING CHEMISTRY PROCESS DESIGN AND DEVELOPMENT, 1966, 5 (03) :322-&
[3]  
HONG YS, 1997, ASME, V119, P313
[4]  
Hsu Y.Y., 1962, J HEAT TRANSF, V84, P207, DOI [10.1115/1.3684339, DOI 10.1115/1.3684339]
[5]  
Kline S.J., 1952, ASME Mechanical Engineering, V75, P3, DOI DOI 10.1016/J.CHAOS.2005.11.046
[6]   Investigation of heat transfer in rectangular microchannels [J].
Lee, PS ;
Garimella, SV ;
Liu, D .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2005, 48 (09) :1688-1704
[7]   Investigation of liquid flow in microchannels [J].
Liu, D ;
Garimella, SV .
JOURNAL OF THERMOPHYSICS AND HEAT TRANSFER, 2004, 18 (01) :65-72
[8]   EFFECT OF DISSOLVED-GASES ON SUBCOOLED FLOW BOILING HEAT-TRANSFER [J].
MULLERSTEINHAGEN, H ;
EPSTEIN, N ;
WATKINSON, AP .
CHEMICAL ENGINEERING AND PROCESSING-PROCESS INTENSIFICATION, 1988, 23 (02) :115-124
[9]  
MURPHY R. W., 1972, P HEAT TRANSF FLUID, P400
[10]  
Shah R.K., 1978, ADV HEAT TRANSFER, V1, DOI 10.1016/B978-0-12-020051-1.50012-7