Optimal instantaneous prediction of voltage instability due to transient faults in power networks taking into account the dynamic effect of generators

被引:33
作者
Khalili, Mohsen [1 ]
Dashtaki, Mohammad Ali [2 ]
Nasab, Morteza Azimi [1 ]
Hanif, Hamid Reza [3 ]
Padmanaban, Sanjeevikumar [1 ,4 ]
Khan, Baseem [5 ]
机构
[1] Aarhus Univ, Dept Business Dev & Technol, CTiF Global Capsule, Herning, Denmark
[2] Amirkabir Univ Technol, Dept Elect Engn, Tehran Polytech, Tehran 158754413, Iran
[3] Iran Univ Sci & Technol IUST, Tehran, Iran
[4] Anna Univ, Ctr Elect Vehicles & Power, KPR Inst Engn & Technol, Dept Elect & Elect Engn, Chennai, Tamil Nadu, India
[5] Hawassa Univ, Dept Elect & Comp Engn, Hawassa, Ethiopia
关键词
Transience; fault forcasting; fault occurrence; induction generator;
D O I
10.1080/23311916.2022.2072568
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Changes in consumption and changes in the structure of the system always occur in each power system. One of the effects of these changes can be the instability of the system voltage. When voltage is unstable, their performance is in conditions of power fluctuations after large errors occur. Determining the voltage stability of traditional methods is time consuming and does not have the necessary efficiency for instantaneous monitoring. In this paper, an index based on the changes of two indices of frequency deviation and frequency response of inertia in the time after the occurrence of perturbation is presented, which has the ability to detect the occurrence of instability and at the same time high speed timely estimation of voltage instability in the power system. In addition, this indicator has been used to determine the appropriate time to start load removal (voltage reduction load). All simulations are performed on the IEEE 33-bus network in DIgSILENT software, the results of which indicate that the proposed index has a very low computational load. Because the proposed method for instantaneous voltage instability prediction does not depend on the network structure and load model and does not require any threshold value. Therefore, the proposed index has a very low computational load. These advantages make the proposed method an interesting option for online and practical applications.
引用
收藏
页数:15
相关论文
共 27 条
[1]  
Fazaeli M.H., IPAPS2022 PAPERS
[2]   Time-domain based fault location for series compensated transmission lines without requiring fault type [J].
Ghazizadeh-Ahsaee, Mahdi .
ELECTRIC POWER SYSTEMS RESEARCH, 2020, 181
[3]  
Gorbunova A., 2020, EMERG SCI J, V4, P539, DOI [10.28991/esj-2020-01251, DOI 10.28991/ESJ-2020-01251]
[4]   Hilbert-Huang transform-based transient busbar protection algorithm [J].
Guo, Zhenwei ;
Yao, Jiangang ;
Tan, Zhewen .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2015, 9 (14) :2032-2039
[5]   Fault Location on Double-Circuit Series-Compensated Lines Using Two-End Unsynchronized Measurements [J].
Izykowski, Jan ;
Rosolowski, Eugeniusz ;
Balcerek, Przemyslaw ;
Fulczyk, Marek ;
Saha, Murari Mohan .
IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (04) :2072-2080
[6]  
Kapeller H., 2021, HighTech Innov. J., V2, P67, DOI 10.28991/HIJ-2021-02-01-07
[7]   Fault location in UPFC compensated double circuit transmission line using negative sequence current phasors [J].
Kundu , Madhumita ;
Debnath, Sudipta .
ELECTRIC POWER SYSTEMS RESEARCH, 2020, 184
[8]   Protection of inverter-based microgrids from ground faults by an innovative directional element [J].
Mahamedi, Behnam ;
Zhu, Jian Guo ;
Eskandari, Mohsen ;
Fletcher, John Edward ;
Li, Li .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2018, 12 (22) :5918-5927
[9]   A Non-unit Protection Scheme for Series-Compensated Transmission System Using Fuzzy Inference System [J].
Mishra, Praveen Kumar ;
Yadav, Anamika .
SMART COMPUTING AND INFORMATICS, 2018, 77 :453-466
[10]  
Nale R., 2016, 2016 INT C CONTROL I