Coupled cooling method and application of latent heat thermal energy storage combined with pre-cooling of envelope: Sensitivity analysis and optimization

被引:29
作者
Gao Xiangkui [1 ]
Yuan Yanping [1 ]
Cao Xiaoling [1 ]
Wu Hongwei [2 ]
Zhao Xudong [3 ]
机构
[1] Southwest Jiaotong Univ, Sch Mech Engn, Chengdu 610031, Peoples R China
[2] Univ Hertfordshire, Sch Engn & Technol, Hatfield AL10 9AB, Herts, England
[3] Univ Hull, Sch Engn, Fac Sci, Kingston Upon Hull HU6 7RX, N Humberside, England
基金
中国国家自然科学基金;
关键词
Coal mine accident; Refuge chamber; Cooling method; Latent Heat Thermal Energy Storage; Surrounding rock; Thermal analysis; PHASE-CHANGE MATERIALS; PERFORMANCE; SIMULATION; EFFICIENCY; REDUCTION; UNIT;
D O I
10.1016/j.psep.2017.03.005
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Cooling system for mine refuge chamber provides comfortable environment for miners to avoid heat damage. The existing cooling systems have their own application scopes and limitations. The coupled cooling method of Latent Heat Thermal Energy Storage (LHTES) combined with pre-cooling of envelope (PE) is a new free cooling method which is suitable for high-temperature, passive, impact and other harsh environment. Then, to improve the thermal comfort and reduce energy consumption, the effect of the pre-cooling temperature, melting temperature of PCM, aspect ratio and amounts of PCM unit on the indoor temperature are investigated in a systematic manner. Furthermore, the system is optimized and the generalized results for the evaluation parameter are given. Analysis of the results may lead to following main conclusions: (i) the method really controls the indoor temperature and the saving amount of PCM is more than 50% compared to the traditional LHTES systems; (ii) the temperature control (TC) performance of PCM would drop significantly if it melts more than 80%; (iii) under current operating conditions, the optimal melting temperature is about 29 degrees C and the aspect ratio of PCM unit is 60:500; (iv) per 1 degrees C the pre-cooling temperature dropped, 19% the actual amount of PCM decreased for the case studied. (C) 2017 Institution of Chemical Engineers. Published by Elsevier B.V. All rights reserved.
引用
收藏
页码:438 / 453
页数:16
相关论文
共 25 条
[1]  
[Anonymous], 2009, INTRO BUILDING FIRE
[2]   Peak load shifting with energy storage and price-based control system [J].
Barzin, Reza ;
Chen, John J. J. ;
Young, Brent R. ;
Farid, Mohammed M. .
ENERGY, 2015, 92 :505-514
[3]   Modeling and simulation of a phase change material system for improving summer comfort in domestic residence [J].
Borderon, Julien ;
Virgone, Joseph ;
Cantin, Richard .
APPLIED ENERGY, 2015, 140 :288-296
[4]   Energy reduction of building air-conditioner with phase change material in Thailand [J].
Chaiyat, Nattaporn ;
Kiatsiriroat, Tanongkiat .
CASE STUDIES IN THERMAL ENGINEERING, 2014, 4 :175-186
[5]  
Dai Guosheng, 1999, HEAT TRANSFER
[6]   Numerical study on the thermal performance of a ventilated facade with PCM [J].
de Gracia, Alvaro ;
Navarro, Lidia ;
Castell, Albert ;
Cabeza, Luisa F. .
APPLIED THERMAL ENGINEERING, 2013, 61 (02) :372-380
[7]   Modeling and parametric analysis of an adsorber unit for thermal energy storage [J].
Fernandes, M. S. ;
Brites, G. J. V. N. ;
Costa, J. J. ;
Gaspar, A. R. ;
Costa, V. A. F. .
ENERGY, 2016, 102 :83-94
[8]   Effectiveness of CFD simulation for the performance prediction of phase change building boards in the thermal environment control of indoor spaces [J].
Gowreesunker, B. L. ;
Tassou, S. A. .
BUILDING AND ENVIRONMENT, 2013, 59 :612-625
[9]   Experimental study on the thermal performance of air-PCM unit [J].
Iten, Muriel ;
Liu, Shuli ;
Shulda, Ashish .
BUILDING AND ENVIRONMENT, 2016, 105 :128-139
[10]   Thermal behavior of cement based plastering mortar containing hybrid microencapsulated phase change materials [J].
Kheradmand, Mohammad ;
Azenha, Miguel ;
de Aguiar, Jose L. B. ;
Krakowiak, Konrad J. .
ENERGY AND BUILDINGS, 2014, 84 :526-536