Improvement of two-phase refrigerant distribution for upward flow of a parallel flow minichannel heat exchanger using insertion devices

被引:13
作者
Kim, Nae-Hyun [1 ]
Kim, Cheol-Hwan [1 ]
Shah, Yousaf [1 ]
Li, Wei [2 ]
机构
[1] Univ Incheon, Dept Mech Engn, Incheon 22012, South Korea
[2] Zhejiang Univ, Dept Energy Engn, Hangzhou 310027, Zhejiang, Peoples R China
关键词
Flow distribution; Parallel flow heat exchanger; Header; Insert device; R-410A; Evaporator; HORIZONTAL HEADERS; ANNULAR-FLOW;
D O I
10.1016/j.applthermaleng.2019.114065
中图分类号
O414.1 [热力学];
学科分类号
摘要
In a parallel flow heat exchanger, significant mal-distribution of flow occurs due to phase separation. In this study, various insert devices (perforated tube, perforated tube with perforated plate, orifice and perforated tube, concentric perforated tube) were investigated to obtain an improved flow distribution in a 36 channel parallel flow heat exchanger. The test section was made to closely simulate an actual heat exchanger. Tests were conducted for upward flow for the mass flux from 57 to 241 kg m(-2) s(-1) and quality from 0.2 to 0.4 using R-410A. Of the investigated insert devices, concentric perforated tube yielded the best flow distribution. Insertion of the concentric perforated tube reduced the thermal degradation from 61% to 14%. Furthermore, the preferred number of holes of the concentric perforated tube was dependent on the mass flux. At a low mass flux, an insert having small number of holes was preferred, whereas the reverse was true at a high mass flux. At a low mass flux, the effect of inlet vapor quality on flow distribution was significant. At a high mass flux, however, the effect of vapor quality on flow distribution was minimal. Possible explanations on the flow distribution behavior were provided through flow visualization in the header.
引用
收藏
页数:14
相关论文
共 27 条
[21]   Two-phase flow distribution in compact heat exchanger manifolds [J].
Vist, S ;
Pettersen, J .
EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2004, 28 (2-3) :209-215
[22]   Characteristics of flow distribution in compact parallel flow heat exchangers, part II: Modified inlet header [J].
Wang, Chi-Chuan ;
Yang, Kai-Shing ;
Tsai, Jhong-Syuan ;
Chen, Ing Youn .
APPLIED THERMAL ENGINEERING, 2011, 31 (16) :3235-3242
[23]  
Watanabe M., 1995, ASMEJSME THERMAL ENG, V2, P35
[24]   Two-phase flow distribution to tubes of parallel flow air-cooled heat exchangers [J].
Webb, RL ;
Chung, K .
HEAT TRANSFER ENGINEERING, 2005, 26 (04) :3-18
[25]   Refrigerant distribution in horizontal headers with downward minichannel-branching conduits: Experiment, empirical correlation and two-phase flow pattern map [J].
Wijayanta, Agung Tri ;
Miyazaki, Takahiko ;
Koyama, Shigeru .
EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2017, 81 :430-444
[26]   Liquid-vapor phase distribution in horizontal headers with upward minichannel-branching conduits [J].
Wijayanta, Agung Tri ;
Miyazaki, Takahiko ;
Koyama, Shigeru .
EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2016, 76 :264-274
[27]   Experiment and visualization on R134a upward flow in the vertical header of microchannel heat exchanger and its effect on distribution [J].
Zou, Yang ;
Hrnjak, Pega S. .