Effects of occupancy and lighting use patterns on lighting energy consumption

被引:134
作者
Yun, Geun Young [1 ]
Kim, Hyoin [1 ]
Kim, Jeong Tai [1 ]
机构
[1] Kyung Hee Univ, Dept Architectural Engn, Yongin 446701, South Korea
基金
新加坡国家研究基金会;
关键词
Occupant behaviour; Energy consumption; Lighting system use; Monitoring study; Daylighting performance; PERFORMANCE; BEHAVIOR; OFFICES; SAVINGS; BLINDS; KOREA; MODEL;
D O I
10.1016/j.enbuild.2011.10.034
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Lighting is one of the largest energy users in artificially lit buildings. In this context, daylighting strategies that potentially reduce the needs of artificial lighting have been highlighted. However, they have not always materialized in practice, which is mainly due to the lack of understanding of occupant perception and behaviour of natural and artificial lighting systems. This study reports survey results from a monitoring campaign of four offices in Korea, which was conducted from February to June 2010 with an aim to reveal occupancy patterns, occupant use of lighting systems, and resulting lighting energy use. The results indicate that there are no statistically significant relationships between external illuminance and lighting use patterns, but there is a clear time of day effects (i.e. a strong tendency of turning on lighting on worker's first arrival in the morning). It has been found that the application of automatic dimming control for lighting with a design illuminance of 500 lx demands to the field studied offices can reduce lighting energy consumption by up to 43%. The study also shows that a change in occupancy patterns observed in this study leads to an increase in lighting energy use by up to 50%. (c) 2011 Elsevier B.V. All rights reserved.
引用
收藏
页码:152 / 158
页数:7
相关论文
共 21 条
[1]  
Bluyssen P., 2009, INDOOR ENV HDB MAKE
[2]   Quantifying energy savings in daylight responsive systems: The role of dimming electronic ballasts [J].
Doulos, L. ;
Tsangrassoulis, A. ;
Topalis, F. .
ENERGY AND BUILDINGS, 2008, 40 (01) :36-50
[3]   On the behaviour and adaptation of office occupants [J].
Haldi, Frederic ;
Robinson, Darren .
BUILDING AND ENVIRONMENT, 2008, 43 (12) :2163-2177
[4]  
Hunt D.R.G., 1979, LIGHTING RES TECHNOL, V12, P21
[5]   A field investigation of the intermediate light switching by users [J].
Lindelöf, D ;
Morel, N .
ENERGY AND BUILDINGS, 2006, 38 (07) :790-801
[6]  
Love J.A., 1998, LIGHTING RES TECHNOL, V30, P45, DOI 10.1177/096032719803000107
[7]   Daylight metrics and energy savings [J].
Mardaljevic, J. ;
Heschong, L. ;
Lee, E. .
LIGHTING RESEARCH & TECHNOLOGY, 2009, 41 (03) :261-283
[8]   The dark side of occupants' behaviour on building energy use [J].
Masoso, O. T. ;
Grobler, L. J. .
ENERGY AND BUILDINGS, 2010, 42 (02) :173-177
[9]   Using field measurements of desktop illuminance in European offices to investigate its dependence on outdoor conditions and its effect on occupant satisfaction, and the use of lights and blinds [J].
Nicol, F ;
Wilson, M ;
Chiancarella, C .
ENERGY AND BUILDINGS, 2006, 38 (07) :802-813
[10]   2-TO-ONE DISCREPANCY BETWEEN MEASURED AND PREDICTED PERFORMANCE OF A LOW-ENERGY OFFICE BUILDING - INSIGHTS FROM A RECONCILIATION BASED ON THE DOE-2 MODEL [J].
NORFORD, LK ;
SOCOLOW, RH ;
HSIEH, ES ;
SPADARO, GV .
ENERGY AND BUILDINGS, 1994, 21 (02) :121-131