Stability Augmentation of a Grid-Connected Wind Farm by Fuzzy-Logic-Controlled DFIG-Based Wind Turbines

被引:21
作者
Hazari, Md. Rifat [1 ]
Mannan, Mohammad Abdul [2 ]
Muyeen, S. M. [3 ]
Umemura, Atsushi [1 ]
Takahashi, Rion [1 ]
Tamura, Junji [1 ]
机构
[1] Kitami Inst Technol KIT, Dept Elect & Elect Engn, 165 Koen Cho, Kitami, Hokkaido 0908507, Japan
[2] Amer Int Univ Bangladesh AIUB, Dept Elect & Elect Engn, Ka 66-1,Kuratoli Rd, Dhaka 1229, Bangladesh
[3] Curtin Univ, Dept Elect & Comp Engn, Perth, WA 6845, Australia
来源
APPLIED SCIENCES-BASEL | 2018年 / 8卷 / 01期
关键词
squirrel cage induction generator (SCIG); doubly fed induction generator (DFIG); fuzzy logic controller (FLC); PI controller; low voltage ride through (LVRT); power system; FAULT-RIDE; VOLTAGE; SYSTEMS; CROWBAR; SCHEME;
D O I
10.3390/app8010020
中图分类号
O6 [化学];
学科分类号
0703 ;
摘要
Wind farm (WF) grid codes require wind generators to have low voltage ride through (LVRT) capability, which means that normal power production should be resumed quickly once the nominal grid voltage has been recovered. However, WFs with fixed-speed wind turbines with squirrel cage induction generators (FSWT-SCIGs) have failed to fulfill the LVRT requirement, which has a significant impact on power system stability. On the other hand, variable-speed wind turbines with doubly fed induction generators (VSWT-DFIGs) have sufficient LVRT augmentation capability and can control the active and reactive power delivered to the grid. However, the DFIG is more expensive than the SCIG due to its AC/DC/AC converter. Therefore, the combined use of SCIGs and DFIGs in a WF could be an effective solution. The design of the rotor-side converter (RSC) controller is crucial because the RSC controller contributes to the system stability. The cascaded control strategy based on four conventional PI controllers is widely used to control the RSC of the DFIG, which can inject only a small amount of reactive power during fault conditions. Therefore, the conventional strategy can stabilize the lower rating of the SCIG. In the present paper, a new control strategy based on fuzzy logic is proposed in the RSC controller of the DFIG in order to enhance the LVRT capability of the SCIG in a WF. The proposed fuzzy logic controller (FLC) is used to control the reactive power delivered to the grid during fault conditions. Moreover, reactive power injection can be increased in the proposed control strategy. Extensive simulations executed in the PSCAD/EMTDC environment for both the proposed and conventional PI controllers of the RSC of the DFIG reveal that the proposed control strategy can stabilize the higher rating of the SCIG.
引用
收藏
页数:24
相关论文
共 32 条
[1]  
Ackermann T, 2005, WIND POWER IN POWER SYSTEMS, P1, DOI 10.1002/0470012684
[2]   Coordinated reactive power management in power networks with wind turbines and FACTS devices [J].
Amaris, Hortensia ;
Alonso, Monica .
ENERGY CONVERSION AND MANAGEMENT, 2011, 52 (07) :2575-2586
[3]  
[Anonymous], 2017, Global Wind Energy Outlook 2016
[4]  
[Anonymous], 1993, INTRO FUZZY CONTROL, DOI DOI 10.1007/978-3-662-11131-4
[5]  
[Anonymous], 2008, IEEE T SYST MAN CYB, DOI DOI 10.1109/TSMC.1979.4310158
[6]  
[Anonymous], 1994, PSCAD EMTDC US MAN
[7]  
Boldea Ion, 2014, 2014 17th International Conference on Electrical Machines and Systems (ICEMS), P1, DOI 10.1109/ICEMS.2014.7013919
[8]   Direct Power Control of DFIG Wind Systems Based on Nonlinear Modeling and Analysis [J].
Bourdoulis, Michael K. ;
Alexandridis, Antonio T. .
IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, 2014, 2 (04) :764-775
[9]  
*E ON NETZ GMBH, 2006, GRID CONN REG HIGH E
[10]  
Global Wind Energy Council (GWEC), 2015, ANN MAK UPD 2015