Thermoeconomic Modeling and Parametric Study of a Photovoltaic-Assisted 1 MWe Combined Cooling, Heating, and Power System

被引:13
作者
Arsalis, Alexandros [1 ,2 ]
Alexandrou, Andreas N. [1 ,2 ]
Georghiou, George E. [2 ,3 ]
机构
[1] Univ Cyprus, Dept Mech & Mfg Engn, CY-1678 Nicosia, Cyprus
[2] Univ Cyprus, FOSS Res Ctr Sustainable Energy, CY-1678 Nicosia, Cyprus
[3] Univ Cyprus, Dept Elect & Comp Engn, CY-1678 Nicosia, Cyprus
关键词
photovoltaic; solar energy; distributed generation; cost analysis; liquefied natural gas; cogeneration; autonomous system; energy efficiency; parametric study; thermoeconomic modeling; ECONOMIC-FEASIBILITY; ENERGY EFFICIENCY; PLANT;
D O I
10.3390/en9080663
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In this study a small-scale, completely autonomous combined cooling, heating, and power (CCHP) system is coupled to a photovoltaic (PV) subsystem, to investigate the possibility of reducing fuel consumption. The CCHP system generates electrical energy with the use of a simple gas turbine cycle, with a rated nominal power output of 1 MWe. The nominal power output of the PV subsystem is examined in a parametric study, ranging from 0 to 600 kW(e), to investigate which configuration results in a minimum lifecycle cost (LCC) for a system lifetime of 20 years of service. The load profile considered is applied for a complex of households in Nicosia, Cyprus. The solar data for the PV subsystem are taken on an hourly basis for a whole year. The results suggest that apart from economic benefits, the proposed system also results in high efficiency and reduced CO2 emissions. The parametric study shows that the optimum PV capacity is 300 kW(e). The minimum lifecycle cost for the PV-assisted CCHP system is found to be 3.509 million (sic), as compared to 3.577 million (sic) for a system without a PV subsystem. The total cost for the PV subsystem is 547,445 (sic), while the total cost for operating the system (fuel) is 731,814 (sic) (compared to 952,201 (sic) for a CCHP system without PVs). Overall the proposed system generates a total energy output of 210,520 kWh (during its whole lifetime), which translates to a unit cost of 17 (sic)/kWh.
引用
收藏
页数:15
相关论文
共 17 条
[1]  
Arsalis A., 2016, P 5 INT C REN EN SOU, P11
[2]  
Arsalis A., 2016, P 5 INT C REN EN SOU, P9
[3]   Thermoeconomic modeling and exergy analysis of a decentralized liquefied natural gas-fueled combined-cooling heating-and-power plant [J].
Arsalis, Alexandros ;
Alexandrou, Andreas .
JOURNAL OF NATURAL GAS SCIENCE AND ENGINEERING, 2014, 21 :209-220
[4]   Design and modeling of 1-10 MWe liquefied natural gas-fueled combined cooling, heating and power plants for building applications [J].
Arsalis, Alexandros ;
Alexandrou, Andreas .
ENERGY AND BUILDINGS, 2015, 86 :257-267
[5]   Modeling and simulation of a 100 kWe HT-PEMFC subsystem integrated with an absorption chiller subsystem [J].
Arsalis, Alexandros .
INTERNATIONAL JOURNAL OF HYDROGEN ENERGY, 2012, 37 (18) :13484-13490
[6]  
Barbose G.L., 2010, Tracking the sun III: The installed price photovoltaics in the U.S. from 1998 to 2009
[8]   A review of thermally activated cooling technologies for combined cooling, heating and power systems [J].
Deng, J. ;
Wang, R. Z. ;
Han, G. Y. .
PROGRESS IN ENERGY AND COMBUSTION SCIENCE, 2011, 37 (02) :172-203
[9]  
Dincer I., 2011, Sustainable energy systems and applications
[10]  
Duffie JA, 2013, SOLAR ENGINEERING OF THERMAL PROCESSES, 4TH EDITION, P1, DOI 10.1002/9781118671603