Dehumidification and thermal regeneration characterization of binary deep eutectic solvents in liquid desiccant air conditioning systems

被引:15
作者
Oladosu, Temidayo L. [1 ]
Al-Kayiem, Hussain H. [1 ]
Gilani, Syed I. U. [1 ]
Baheta, Aklilu T. [1 ]
机构
[1] Univ Teknol PETRONAS, Dept Mech Engn, Ipoh 32610, Perak, Malaysia
关键词
Biocompatibility; Deep eutectic solvents; Dehumidification; Greener solvents. liquid desiccants; Thermal regenerations; IONIC LIQUIDS; PRESSURE; DESIGN; WATER;
D O I
10.1016/j.jobe.2021.103056
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The energy-saving propensity of liquid desiccant air dehumidification technique compared with its counterparts, mitigating the limitations of conventional desiccant solutions and the need for energy optimization in indoor space cooling, has invigorated the exploration of alternative desiccant solutions. This study investigates different binary deep eutectic solvents as a potential alternative working fluids in liquid desiccant air conditioning systems. Hydrogen bond acceptors (Choline chloride, N, N-Diethylethanolammonium chloride, 1-Butyl-3-methylimidazolium chloride, ZnCl2) and hydrogen bond donor (Ethylene glycol) were synthesized in different ratios to form binary deep eutectic solvents. The physiochemical, thermophysical and rheological properties of the investigated solutions were characterized and evaluated. DES A1 (mixture of choline chloride and ethylene glycol in ratio 1:2) and DES D1 (1-Butyl-3-methylimidazolium chloride and ethylene glycol in ratio 1:1) were found best among investigated binary DES solutions. The dehumidification and thermal regeneration potential of these promising solutions were further investigated in a humidity chamber and a drying oven, respectively. At 65 % relative humidity, 30 degrees C air temperature, and 3.77 x 10(-4) m(2) moisture-desiccant contact area, the estimated dehumidification mass flux of DES A1and DES D1 are 4.61 x 10(-2) and 3 x 10(-2) g/m(2) .s, respectively. Empirical correlations obtained for deep eutectic solvents moisture absorption in this study provide an error limit between +/- 2.6 % to +/- 3.5 %. These solutions are found promising as alternative solutions for dehumidification and thermal regeneration.
引用
收藏
页数:14
相关论文
共 44 条
[1]   Comparative evaluation on the thermal properties and stability of MWCNT nanofluid with conventional surfactants and ionic liquid [J].
Bakthavatchalam, Balaji ;
Habib, Khairul ;
Wilfred, Cecilia D. ;
Saidur, R. ;
Saha, Bidyut Baran .
JOURNAL OF THERMAL ANALYSIS AND CALORIMETRY, 2022, 147 (01) :393-408
[2]  
Batukray J.D., 2019, J ENV PROTECTION SUS, V5, P1
[3]   Experimental investigation on vapor pressure of desiccant for air conditioning application [J].
Bouzenada, S. ;
Frainkin, L. ;
Leonard, A. .
8TH INTERNATIONAL CONFERENCE ON AMBIENT SYSTEMS, NETWORKS AND TECHNOLOGIES (ANT-2017) AND THE 7TH INTERNATIONAL CONFERENCE ON SUSTAINABLE ENERGY INFORMATION TECHNOLOGY (SEIT 2017), 2017, 109 :817-824
[4]  
Bp B, EN OUTL 2018 ED
[5]   Ultrasound-assisted extraction of phenolic compounds from avocado leaves (Persea americana Mill. var. Drymifolia): optimization and modeling [J].
Che-Galicia, Gamaliel ;
Vaquiro-Herrera, Henry A. ;
Sampieri, Alvaro ;
Corona-Jimenez, Edith .
INTERNATIONAL JOURNAL OF CHEMICAL REACTOR ENGINEERING, 2020, 18 (07)
[6]   Thermal Conductivity of Ionic Liquids at Atmospheric Pressure: Database, Analysis, and Prediction Using a Topological Index Method [J].
Chen, Qiao-Li ;
Wu, Ke-Jun ;
He, Chao-Hong .
INDUSTRIAL & ENGINEERING CHEMISTRY RESEARCH, 2014, 53 (17) :7224-7232
[7]  
Chen X., 2020, ENERGY BUILT ENV, V1, P106, DOI DOI 10.1016/J.ENBENV.2019.09.001
[8]   Experimental study of a membrane-based dehumidification cooling system [J].
Chen, Ziwei ;
Zhu, Jie ;
Bai, Hongyu ;
Yan, Yuying ;
Zhang, Lizhi .
APPLIED THERMAL ENGINEERING, 2017, 115 :1315-1321
[9]   Ionic liquid-based hybrid absorption cycle for water heating, dehumidification, and cooling [J].
Chugh, Devesh ;
Gluesenkamp, Kyle ;
Abdelaziz, Omar ;
Moghaddam, Saeed .
APPLIED ENERGY, 2017, 202 :746-754
[10]   Properties of aqueous solutions of lithium and calcium chlorides: formulations for use in air conditioning equipment design [J].
Conde, MR .