Wavelet-Like Transform to Optimize the Order of an Autoregressive Neural Network Model to Predict the Dissolved Gas Concentration in Power Transformer Oil from Sensor Data

被引:11
作者
Bezerra, Francisco Elanio [1 ]
Zemuner Garcia, Fernando Andre [2 ]
Nabeta, Silvio Ikuyo [3 ]
Martha de Souza, Gilberto Francisco [3 ]
Chabu, Ivan Eduardo [3 ]
Santos, Josemir Coelho [3 ]
Nagao Junior, Shigueru [3 ]
Pereira, Fabio Henrique [1 ,2 ,3 ]
机构
[1] Univ Nove de Julho UNINOVE, Ind Engn Grad Program, BR-01525000 Sao Paulo, Brazil
[2] Univ Nove de Julho UNINOVE, Informat & Knowledge Management Grad Program, BR-01525000 Sao Paulo, Brazil
[3] Univ Sao Paulo EPUSP, Polytech Sch, BR-05508010 Sao Paulo, Brazil
关键词
dissolved gas analysis; power transformers; wavelet-like transform; autoregressive model; ALGORITHM;
D O I
10.3390/s20092730
中图分类号
O65 [分析化学];
学科分类号
070302 ; 081704 ;
摘要
Dissolved gas analysis (DGA) is one of the most important methods to analyze fault in power transformers. In general, DGA is applied in monitoring systems based upon an autoregressive model; the current value of a time series is regressed on past values of the same series, as well as present and past values of some exogenous variables. The main difficulty is to decide the order of the autoregressive model; this means determining the number of past values to be used. This study proposes a wavelet-like transform to optimize the order of the variables in a nonlinear autoregressive neural network to predict the in oil dissolved gas concentration (DGC) from sensor data. Daubechies wavelets of different lengths are used to create representations with different time delays of ten DGC, which are then subjected to a procedure based on principal components analysis (PCA) and Pearson's correlation to find out the order of an autoregressive model. The representations with optimal time delays for each DGC are applied as input in a multi-layer perceptron (MLP) network with backpropagation algorithm to predict the gas at the present and future times. This approach produces better results than choosing the same time delay for all inputs, as usual. The forecasts reached an average mean absolute percentage error (MAPE) of 5.763%, 1.525%, 1.831%, 2.869%, and 5.069% for C2H2, C2H6, C2H4, CH4, and H-2, respectively.
引用
收藏
页数:14
相关论文
共 39 条
  • [1] A Review of Dissolved Gas Analysis Measurement and Interpretation Techniques
    Abu Bakar, Norazhar
    Abu-Siada, A.
    Islam, S.
    [J]. IEEE ELECTRICAL INSULATION MAGAZINE, 2014, 30 (03) : 39 - 49
  • [2] [Anonymous], GUIDE TRANSFORMER MA
  • [3] Power transformer fault diagnosis based on dissolved gas analysis by support vector machine
    Bacha, Khmais
    Souahlia, Seifeddine
    Gossa, Moncef
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2012, 83 (01) : 73 - 79
  • [4] Properties of sufficiency and statistical tests
    Bartlett, MS
    [J]. PROCEEDINGS OF THE ROYAL SOCIETY OF LONDON SERIES A-MATHEMATICAL AND PHYSICAL SCIENCES, 1937, 160 (A901) : 0268 - 0282
  • [5] Box G.E.P., 2015, TIME SERIES ANAL FOR, P756
  • [6] Dissolved Gas Analysis Equipment for Online Monitoring of Transformer Oil: A Review
    Bustamante, Sergio
    Manana, Mario
    Arroyo, Alberto
    Castro, Pablo
    Laso, Alberto
    Martinez, Raquel
    [J]. SENSORS, 2019, 19 (19)
  • [7] STUDY OF A MEASURE OF SAMPLING ADEQUACY FOR FACTOR-ANALYTIC CORRELATION MATRICES
    CERNY, BA
    KAISER, HF
    [J]. MULTIVARIATE BEHAVIORAL RESEARCH, 1977, 12 (01) : 43 - 47
  • [8] Chakravorti S, 2013, POWER SYST, P1, DOI 10.1007/978-1-4471-5550-8
  • [9] Dissolved Gas Analysis in Transformer Oil Using Pt-Doped WSe2 Monolayer Based on First Principles Method
    Chen, Zhenwei
    Zhang, Xiaoxing
    Xiong, Hao
    Chen, Dachang
    Cheng, Hongtu
    Tang, Ju
    Tian, Yuan
    Xiao, Song
    [J]. IEEE ACCESS, 2019, 7 : 72012 - 72019
  • [10] Dissolved Gas Analysis Principle-Based Intelligent Approaches to Fault Diagnosis and Decision Making for Large Oil-Immersed Power Transformers: A Survey
    Cheng, Lefeng
    Yu, Tao
    [J]. ENERGIES, 2018, 11 (04)