First-principles modeling of frost accumulation on fan-supplied tube-fin evaporators

被引:36
作者
da Silva, Diogo L. [2 ]
Hermes, Christian J. L. [1 ]
Melo, Claudio [2 ]
机构
[1] Univ Fed Parana, Dept Mech Engn, Appl Thermodynam Res Ctr, BR-81531990 Curitiba, Parana, Brazil
[2] Univ Fed Santa Catarina, Dept Mech Engn, POLO Res Labs Cooling & Thermophys, BR-88040970 Florianopolis, SC, Brazil
关键词
Frost formation; Evaporator; Fan-coil; Tube-fin; Modeling; Simulation; HEAT-EXCHANGERS; PART I; BEHAVIOR; PERFORMANCE;
D O I
10.1016/j.applthermaleng.2011.04.029
中图分类号
O414.1 [热力学];
学科分类号
摘要
The present paper investigates the frost formation on air-supplied tube-fin evaporator coils under typical operating conditions of light commercial refrigerating appliances. To this end, a first-principles simulation model based on air-side mass, energy and momentum balances was put forward to predict the evaporator frosting over time. Experiments were also carried out to gather key data for the model validation exercise. The numerical results were compared with the experimental air-side pressure drop, air-flow rate, cooling capacity, and accumulated frost mass, with all predictions falling within the experimental uncertainty range. The model was then used to investigate the evaporator thermal-hydraulic performance under frosting conditions accounting for the non-linear effect induced by the combination of the frosted evaporator and the fan-supplied air-flow rate. The effects of progressive frost clogging and low conductivity frost layer on the overall thermal resistance were also assessed. It was found that the former is the main cause of cooling capacity reduction under frosting conditions. (C) 2011 Elsevier Ltd. All rights reserved.
引用
收藏
页码:2616 / 2621
页数:6
相关论文
共 19 条
[1]  
Albert M., 2008, 9 INT IEA HEAT PUMP
[2]  
Aljuwayhel N.F., 2006, THESIS U WISCONSIN M
[3]   Fan supplied heat exchanger fin performance under frosting conditions [J].
Chen, H ;
Thomas, L ;
Besant, RW .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2003, 26 (01) :140-149
[4]   A new time- and space-dependent model for predicting frost formation [J].
Cui, J. ;
Li, W. Z. ;
Liu, Y. ;
Jiang, Z. Y. .
APPLIED THERMAL ENGINEERING, 2011, 31 (04) :447-457
[5]   Experimental study of frost accumulation on fan-supplied tube-fin evaporators [J].
da Silva, Diogo L. ;
Hermes, Christian J. L. ;
Melo, Claudio .
APPLIED THERMAL ENGINEERING, 2011, 31 (6-7) :1013-1020
[6]   A study of frost growth and densification on flat surfaces [J].
Hermes, Christian J. L. ;
Piucco, Robson O. ;
Barbosa, Jader R., Jr. ;
Melo, Claudio .
EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2009, 33 (02) :371-379
[7]   Effect of surface treatments on the frosting/defrosting behavior of a fin-tube heat exchanger [J].
Jhee, S ;
Lee, KS ;
Kim, WS .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2002, 25 (08) :1047-1053
[8]  
Kondepudi S.N., 1987, ASHRAE T, V93, P258
[9]   A one-dimensional model for frost formation on a cold flat surface [J].
Lee, KS ;
Kim, WS ;
Lee, TH .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 1997, 40 (18) :4359-4365
[10]   Prediction of an effective cooling output of the fin-and-tube heat exchanger under frosting conditions [J].
Lenic, Kristian ;
Trp, Anica ;
Frankovic, Bernard .
APPLIED THERMAL ENGINEERING, 2009, 29 (11-12) :2534-2543