The Effect of Metal Foam Thickness on Jet Array Impingement Heat Transfer in High-Porosity Aluminum Foams

被引:27
作者
Singh, Prashant [1 ]
Nithyanandam, Karthik [2 ]
Zhang, Mingyang [3 ]
Mahajan, Roop L. [4 ,5 ]
机构
[1] Mississippi State Univ, Dept Mech Engn, Starkville, MS 39762 USA
[2] Element 16 Technol Inc, Engn, Arcadia, CA 91006 USA
[3] Virginia Tech, Dept Mech Engn, Blacksburg, VA 24061 USA
[4] Virginia Tech, Dept Mech Engn, Engn, Blacksburg, VA 24061 USA
[5] 420 Mech Engn,7054 Haycock Rd, Falls Church, VA 22043 USA
来源
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME | 2020年 / 142卷 / 05期
关键词
Jet impingement; metal foam; heat transfer coefficient; electronic cooling; NATURAL-CONVECTION; FORCED-CONVECTION; FLOW; SINKS;
D O I
10.1115/1.4045640
中图分类号
O414.1 [热力学];
学科分类号
摘要
High-porosity metal foam (MF) is a popular option for high-performance heat exchangers as it offers significantly higher heat transfer participation area per unit volume compared to other convection enhancement cooling methods. Further, metal foams provide highly tortuous flow paths resulting in thermal dispersion assisted by enhanced mixing. This paper presents experimental and numerical studies and the detailed underlying physics of jet array impingement onto high-porosity ( epsilon similar to 0.95) thin aluminum foams. The jet and foam configurations were designed for the maximum utilization of the foam area for heat transfer and reduced penalty on the pumping power requirement. Three different pore density foams were tested with three different array-jet impingement configurations. The minimum possible thickness for each pore density was tested, viz., 5 pores-per-inch (PPI): 19mm, 10 PPI: 12.7mm, and 20 PPI: 6.35mm. The baseline case for these foam-based jet impingement configurations was the corresponding configuration of orthogonal jet impingement onto a smooth heated surface, where the distance between the jet-issuing plane and the heated surface was maintained at the foam thickness level. In general, thinner foams facilitated greater jet penetration and increased foam volume usage, resulting in higher heat transfer rates for a given pore density, especially when combined with jet configurations with larger open areas. Finally, we evaluated the thermal hydraulic performance for different foam configurations and the optimum value of a given PPI was found to be at an intermediate rather than the lowest foam thickness.
引用
收藏
页数:15
相关论文
共 35 条
[1]  
Alhusseny A.N.M., 2018, POROSITY PROCESS TEC, P181, DOI DOI 10.5772/INTECHOPEN.70451
[2]   The effect of open-cell metal foams strut shape on convection heat transfer and pressure drop [J].
Ambrosio, Giuseppe ;
Bianco, Nicola ;
Chiu, Wilson K. S. ;
Iasiello, Marcello ;
Naso, Vincenzo ;
Oliviero, Maria .
APPLIED THERMAL ENGINEERING, 2016, 103 :333-343
[3]   Analytical and numerical prediction of heat transfer and pressure drop in open-cell metal foams [J].
Bai, Mo ;
Chung, J. N. .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2011, 50 (06) :869-880
[4]   Metal foam and finned metal foam heat sinks for electronics cooling in buoyancy-induced convection [J].
Bhattacharya, A. ;
Mahajan, R. L. .
JOURNAL OF ELECTRONIC PACKAGING, 2006, 128 (03) :259-266
[5]   Finned metal foam heat sinks for electronics cooling in forced convection [J].
Bhattacharya, A ;
Mahajan, RL .
JOURNAL OF ELECTRONIC PACKAGING, 2002, 124 (03) :155-163
[6]   Thermophysical properties of high porosity metal foams [J].
Bhattacharya, A ;
Calmidi, VV ;
Mahajan, RL .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2002, 45 (05) :1017-1031
[7]   Metal foams as compact high performance heat exchangers [J].
Boomsma, K ;
Poulikakos, D ;
Zwick, F .
MECHANICS OF MATERIALS, 2003, 35 (12) :1161-1176
[8]  
Calmidi V.V, 1998, TRANSPORT PHENOMENA
[9]   The effective thermal conductivity of high porosity fibrous metal foams [J].
Calmidi, VV ;
Mahajan, RL .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1999, 121 (02) :466-471
[10]   Forced convection in high porosity metal foams [J].
Calmidi, VV ;
Mahajan, RL .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 2000, 122 (03) :557-565