A novel VSC-HVDC link model for dynamic power system simulations

被引:9
作者
Castro, Luis M. [1 ]
Acha, Enrique [1 ]
Fuerte-Esquivel, Claudio R. [2 ]
机构
[1] Tampere Univ Technol, Dept Elect Engn, FIN-33101 Tampere, Finland
[2] Univ Michoacana, Fac Elect Engn, Morelia, Michoacan, Mexico
关键词
VSC; HVDC; FACTS; Newton-Raphson method; Dynamic power system simulations;
D O I
10.1016/j.epsr.2015.05.003
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper introduces a new RMS model of the VSC-HVDC link. The model is useful for assessing the steady-state and dynamic responses of large power systems with embedded back-to-back and point-to-point VSC-HVDC links. The VSC-HVDC model comprises two voltage source converters (VSC) linked by a DC cable. Each VSC is modelled as an ideal phase-shifting transformer whose primary and secondary windings correspond, in a notional sense, to the AC and DC buses of the VSC. The magnitude and phase angle of the ideal phase-shifting transformer represent the amplitude modulation ratio and the phase shift that exists in a PWM converter to enable either generation or absorption of reactive power purely by electronic processing of the voltage and current waveforms within the VSC. The mathematical model is formulated in such away that the back-to-back VSC-HVDC model is realized by simply setting the DC cable resistance to zero in the point-to-point VSC-HVDC model. The Newton-Raphson method is used to solve the nonlinear algebraic and discretised differential equations arising from the VSC-HVDC, synchronous generators and the power grid, in a unified frame-of-reference for efficient, iterative solutions at each time step. The dynamic response of the VSC-HVDC model is assessed thoroughly; it is validated against the response of a detailed EMT-type model using Simulink (R). The solution of a relatively large power system shows the ability of the new dynamic model to carry out large-scale power system simulations with high efficiency. (C) 2015 Elsevier B.V. All rights reserved.
引用
收藏
页码:111 / 120
页数:10
相关论文
共 50 条
[21]   Interaction Assessment and Stability Analysis of the MMC-Based VSC-HVDC Link [J].
Dadjo Tavakoli, Saman ;
Prieto-Araujo, Eduardo ;
Sanchez-Sanchez, Enric ;
Gomis-Bellmunt, Oriol .
ENERGIES, 2020, 13 (08)
[22]   Study on A Hybrid Fuzzy-PI Controller Applied to VSC-HVDC System [J].
Geng Yuancheng ;
Li Zhixiong ;
Zhang Jiangcheng .
2010 2ND INTERNATIONAL ASIA CONFERENCE ON INFORMATICS IN CONTROL, AUTOMATION AND ROBOTICS (CAR 2010), VOL 2, 2010, :484-487
[23]   Control functions for a radially operated three-terminal VSC-HVDC system [J].
Iaria, A. ;
Rapizza, M. R. ;
Marzinotto, M. .
2018 IEEE INTERNATIONAL CONFERENCE ON INDUSTRIAL TECHNOLOGY (ICIT), 2018, :1679-1684
[24]   A control strategy for three-level VSC-HVDC system [J].
Liu, HT ;
Xu, Z ;
Gao, Z .
2002 IEEE POWER ENGINEERING SOCIETY SUMMER MEETING, VOLS 1-3, CONFERENCE PROCEEDINGS, 2002, :480-485
[25]   Impact of VSC-HVDC Reactive Power Control Schemes on Voltage Stability [J].
Bernat, Josep Oriol ;
Preece, Robin .
2019 IEEE MILAN POWERTECH, 2019,
[26]   A New Technology for HVDC Start-up and Operation Using VSC-HVDC System [J].
Guo, Chunyi ;
Zhao, Chengyong .
2009 IEEE POWER & ENERGY SOCIETY GENERAL MEETING, VOLS 1-8, 2009, :960-+
[27]   Impedance Modelling and Parametric Sensitivity of a VSC-HVDC System: New Insights on Resonances and Interactions [J].
Agbemuko, Adedotun J. ;
Luis Dominguez-Garcia, Jose ;
Prieto-Araujo, Eduardo ;
Gomis-Bellmunt, Oriol .
ENERGIES, 2018, 11 (04)
[28]   Power Oscillation Damping from VSC-HVDC Connected Offshore Wind Farms using DC Link Braking Chopper [J].
Wang, Minxiao ;
Manchola, Alvaro Jose Hernandez ;
Raab, Alexander ;
Mehlmann, Gert ;
Luther, Matthias .
2023 25TH EUROPEAN CONFERENCE ON POWER ELECTRONICS AND APPLICATIONS, EPE'23 ECCE EUROPE, 2023,
[29]   Small Signal Assessment of An AC System Integrated With A VSC-HVDC Network [J].
Duc Nguyen Huu .
IEEE EUROCON 2015 - INTERNATIONAL CONFERENCE ON COMPUTER AS A TOOL (EUROCON), 2015, :490-495
[30]   A kind of harmonic suppression controller used in VSC-HVDC transmission system [J].
Hu, Yongyin ;
Li, Xingyuan ;
Zhou, Hongyu ;
Li, Kuan ;
Gu, Chao .