Intrinsic hetero-polar surface charge phenomenon in environmental friendly C3F7CN/CO2 gas mixture

被引:33
作者
Chen, Geng [1 ]
Tu, Youping [1 ]
Wu, Shaocong [1 ]
Lin, Chuanjie [2 ]
Qin, Sichen [1 ]
Li, Chuanyang [2 ]
He, Jinliang [2 ]
机构
[1] North China Elect Power Univ, Key Lab Alternate Elect Power Syst Renewable Ener, Beinong Rd 2, Beijing 102206, Peoples R China
[2] Tsinghua Univ, Dept Elect Engn, State Key Lab Power Syst, Beijing 100084, Peoples R China
基金
中国国家自然科学基金;
关键词
charge accumulation; surface charge; C3F7CN/CO2; SF6; alternatives; HVDC; SULFUR-HEXAFLUORIDE; SF6; IONIZATION; COEFFICIENTS; INSULATOR; FLASHOVER;
D O I
10.1088/1361-6463/ab7565
中图分类号
O59 [应用物理学];
学科分类号
摘要
The hetero-polar charges on the spacer surface due to the gas ionization has been verified as one of the hazard charge sources threatening the safe operation of HVDC gas-insulated transmission line (GIL). This letter reports the differences in surface charging properties of spacers in SF6 and C3F7CN/CO2 gas mixtures, and a rigorous re-examination of environmental firendly gas assessment for DC GIL is introduced. The results show that when the maximum value of electrical field strength at the spacer surface is in 0.45 kV mm(-1), homo-polar surface potential in different insulating gases indicates a dominant charge originating from bulk injection. As the maximum value of electrical field strength at the spacer surface reaches 0.68 kV mm(-1), local hetero-polar surface potential areas are detected and the area ratio of these regions is higher in CO2 gas, followed by 4% C3F7CN/96% CO2 gas mixtures. While in the 10% C3F7CN/90% CO2 gas mixtures, homo-polar potential regions are still dominant with very low area ratio of hetero-polar potential regions, which is close to that measured in SF6. An indicating factor is put forward to further clarify the key role of hetero-polar charges plays in potentially triggering surface flashover. This letter provides an important basis for determining contents and components of insulating gases, which serves as one of the key issues in developing HVDC GIL.
引用
收藏
页数:5
相关论文
共 26 条
[1]  
3M, 2015, TECHNICAL DATA
[2]   MEASUREMENT OF IONIZATION AND ATTACHMENT COEFFICIENTS IN SULPHUR HEXAFLUORIDE IN UNIFORM FIELDS [J].
BHALLA, MS ;
CRAGGS, JD .
PROCEEDINGS OF THE PHYSICAL SOCIETY OF LONDON, 1962, 80 (513) :151-&
[3]   Environment-friendly Insulating Gases for HVDC Gas-insulated Transmission Lines [J].
Chen, Geng ;
Tu, Youping ;
Wang, Cong ;
Wang, Jue ;
Yuan, Zhikang ;
Ma, Guoming ;
Wang, Jian ;
Qi, Bo ;
Li, Chuanyang .
CSEE JOURNAL OF POWER AND ENERGY SYSTEMS, 2021, 7 (03) :510-529
[4]   CHARGING OF INSULATOR SURFACES BY IONIZATION AND TRANSPORT IN GASES [J].
COOKE, CM .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1982, 17 (02) :172-178
[5]   Sulfur Hexafluoride (SF6) Emission Estimates for China: An Inventory for 1990-2010 and a Projection to 2020 [J].
Fang, Xuekun ;
Hu, Xia ;
Janssens-Maenhout, Greet ;
Wu, Jing ;
Han, Jiarui ;
Su, Shenshen ;
Zhang, Jianbo ;
Hu, Jianxin .
ENVIRONMENTAL SCIENCE & TECHNOLOGY, 2013, 47 (08) :3848-3855
[6]  
Fujimoto N, 1987, P 5 INT S GAS DIEL
[7]   Research on influences of contact force in chemical mechanical polishing (CMP) process [J].
Han, Lei ;
Zhao, Hongwei ;
Zhang, Qixun ;
Jin, Mingjun ;
Zhang, Lin ;
Zhang, Peng .
AIP ADVANCES, 2015, 5 (04)
[8]   Green Gas to Replace SF6 in Electrical Grids [J].
Kieffel, Yannick ;
Irwin, Todd ;
Ponchon, Philippe ;
Owens, John .
IEEE POWER & ENERGY MAGAZINE, 2016, 14 :32-39
[9]   Technical Aspects of Gas Insulated Transmission Lines and Application of New Insulating Gases [J].
Koch, Hermann ;
Goll, Felix ;
Magier, Tomasz ;
Juhre, Karsten .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2018, 25 (04) :1448-1453
[10]   DC Flashover Characteristics of a Polymeric Insulator in Presence of Surface Charges [J].
Kumara, Sarath ;
Alam, Shahid ;
Hoque, Imtiaz R. ;
Serdyuk, Yuriy V. ;
Gubanski, Stanislaw M. .