Accelerated-ageing test for RTV-coated insulators: analysis of electrical and material properties

被引:5
作者
Devendranath, D
Aravind, KA
Ramulu, A
Tripathy, AK
机构
[1] Cent Power Res Inst, UHV Res Lab, Hyderabad 500039, Andhra Pradesh, India
[2] Cent Power Res Inst, Bangalore 560080, Karnataka, India
关键词
D O I
10.1049/ip-gtd:20045188
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
An accelerated-ageing test is conducted on three room-temperature-vulcanised (RTV) coated porcelain insulators, until the initiation of ageing phenomena, in a salt-fog-ageing test chamber. The test conducted was similar to the IEC 1109 1000 h test, but with scaled-down test setup parameters to address criticisms published in the literature. The results obtained prove the effectiveness of the hydrophobicity of the surface in terms of electrical and material properties. The electrical properties were obtained by online monitoring of the leakage current. The material characteristics were evaluated by conducting energy-dispersion X-ray (EDX) analysis and X-ray diffraction (XRD) analysis. In addition, the fog dynamics in the test chamber on the direct fog (DF) sample, which is in the axis of nozzle columns, and indirect fog samples IF1 and IF2, which were slightly away from the nozzle column axis, was evaluated. It was concluded that the RTV-coated samples which were kept away from the nozzle-column axis, i.e. IF1 and IF2 samples, showed symptoms of initiation of ageing earlier than the sample which was in direct fog mode.
引用
收藏
页码:635 / 644
页数:10
相关论文
共 28 条
[1]   ROLE OF THE SIZE OF PARTICLES OF ALUMINA-TRIHYDRATE FILLER ON THE LIFE OF RTV SILICONE-RUBBER COATING [J].
DENG, H ;
HACKAM, R ;
CHERNEY, EA .
IEEE TRANSACTIONS ON POWER DELIVERY, 1995, 10 (02) :1012-1024
[2]   Development and application of a multi channel current integrator-cum-peak classifier for online monitoring of leakage current on RTV coated insulators [J].
Devendranath, D ;
Girija, G ;
Aradhya, RSS ;
Gunasekaran, B ;
Bhaskaran, A .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2005, 152 (02) :247-252
[3]   Leakage current and charge in RTV coated insulators under pollution conditions [J].
Devendranath, D ;
Channakeshava ;
Rajkumar, AD .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2002, 9 (02) :294-299
[4]  
DEVENDRANATH D, 2001, 12 INT S HIGH VOLT E, P671
[5]  
DEVENDRANATH D, 1999, CIGRE C LUC SWITZ
[6]  
GORUR GS, 1990, IEEE T
[7]   AGING IN SILICONE-RUBBER USED FOR OUTDOOR INSULATION [J].
GORUR, RS ;
KARADY, GG ;
JAGOTA, A ;
SHAH, M ;
YATES, AM ;
SCHNEIDER, HM ;
DETOURREIL, C ;
MACKEVICH, JP ;
HOFFMAN, JW ;
ORBECK, T ;
AMBURGEY, G ;
ROKOS, G ;
TOSKEY, GA ;
MUELLER, PR ;
TAY, R ;
WINTER, HJ .
IEEE TRANSACTIONS ON POWER DELIVERY, 1992, 7 (02) :525-538
[8]  
GORUR RS, 1994, 15107 CIGRE
[9]  
GORUR RS, 2000, INSUL NEWS MARK REP, V8, P54
[10]   Experience with IEC 1109 1000 h salt fog ageing test for composite insulators [J].
Gutman, I ;
Hartings, R ;
Matsuoka, R ;
Kondo, K .
IEEE ELECTRICAL INSULATION MAGAZINE, 1997, 13 (03) :36-39