New impedance-based fault location method for unbalanced power distribution systems

被引:11
作者
Alwash, Shamam F. [1 ]
Ramachandaramurthy, Vigna K. [1 ]
机构
[1] Univ Tenaga Nas, Dept Elect Power Engn, Power Qual Res Grp, Kajang 43000, Selangor, Malaysia
关键词
fault location; power distribution faults; power system protection; CIRCUIT ANALYSIS;
D O I
10.1002/etep.1885
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a novel formulation of impedance-based fault location method for overhead unbalanced distribution systems. The proposed method uses a general fault location equation that is applicable to all possible single and compound shunt fault types. This is in contrast with existing impedance-based methods which use an equation for each fault type and do not cover all types. The proposed method also overcomes the limitation of the conventional method, which requires the identification of fault type. Only the fundamental values of voltages and current measured at the substation terminal are required for the proposed method. The single-phase and three-phase laterals and the capacitive effect of distribution line are considered in this paper. The proposed method was evaluated and tested on a modified IEEE 34-bus distribution system using PSCAD/EMTDC software. Test results verify the accuracy and robustness of the proposed method. Copyright (c) 2014 John Wiley & Sons, Ltd.
引用
收藏
页码:1008 / 1021
页数:14
相关论文
共 28 条
[1]   New concept in fault location for overhead distribution systems using superimposed components [J].
Aggarwal, RK ;
Aslan, Y ;
Johns, AT .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 1997, 144 (03) :309-316
[2]  
[Anonymous], EL DISTR 2005 CIRED
[3]   Location of faults in power distribution laterals using superimposed components and programmable logic controllers [J].
Aslan, Yilmaz ;
Ture, Sebnem .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2011, 33 (04) :1003-1011
[4]  
Ben-Israels A, 2003, GEN INVERSES THEORY
[5]   A new fault location algorithm using direct circuit analysis for distribution systems [J].
Choi, MS ;
Lee, SJ ;
Lee, DS ;
Jin, BG .
IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (01) :35-41
[6]   A direct three-phase circuit analysis-based fault location for line-to-line fault [J].
Choi, Myeon-Song ;
Lee, Seung-Jae ;
Lim, Seong-Il ;
Lee, Duck-Su ;
Yang, Xia .
IEEE TRANSACTIONS ON POWER DELIVERY, 2007, 22 (04) :2541-2547
[7]  
Dagenharts J., 1999, IEEE RUR EL POW C MA, DOI [10.1109/REPCON.1999.768690, DOI 10.1109/REPCON.1999.768690]
[8]   Fuzzy logic-based fault-type identification in unbalanced radial power distribution system [J].
Das, B .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (01) :278-285
[9]  
Das R, 2000, 2000 IEEE POWER ENGINEERING SOCIETY SUMMER MEETING, CONFERENCE PROCEEDINGS, VOLS 1-4, P443, DOI 10.1109/PESS.2000.867627
[10]  
Dass R, 1995, C P COMM POW COMP MA, P6, DOI [10.1109/WESCAN.1995.493936, DOI 10.1109/WESCAN.1995.493936]