A new hybrid method for on-line dynamic security assessment

被引:2
作者
Cheung, KW [1 ]
机构
[1] Cegelec ESCA Corp, Bellevue, WA 98004 USA
关键词
transient stability assessment; on-line security analysis; energy management systems;
D O I
10.1016/S0967-0661(98)00095-1
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
This paper presents a new hybrid method called marginally unstable injection (MUI). This method incorporates energy function analysis into a time-domain simulator for transient stability assessment. Using a 'controlled' sequence of short pseudo-faults and the concept of slow energy function (SEF), the proposed method provides an improved stability index by impelling a stable system to a marginally unstable state. The resulting stability index is then utilized for estimating the amount of generation rejection required to maintain transient stability within the framework of on-line dynamic security assessment. The technique developed is applied to a 700-bus North America system. (C) 1998 Elsevier Science Ltd. AII rights reserved.
引用
收藏
页码:1373 / 1380
页数:8
相关论文
共 35 条
[31]   A measurement-simulation hybrid method for transient stability assessment and control based on the deviation energy [J].
Ma, Shiying ;
Chen, Changsheng ;
Liu, Chengxi ;
Shen, Zhengwei .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2020, 115
[32]   A Data-Driven Scheme Based on Sparse Projection Oblique Randomer Forests for Real-Time Dynamic Security Assessment [J].
Lin, Yanfeng ;
Wang, Xinyao .
IEEE ACCESS, 2022, 10 :79469-79479
[33]   A new method of transient stability assessment in power systems using LS-SVM [J].
Izzri, A. W. Noor ;
Mohamed, Azah ;
Yahya, Iskandar .
2007 5TH STUDENT CONFERENCE ON RESEARCH AND DEVELOPMENT, 2007, :12-+
[34]   Hybrid Analytical and Data-Driven Model Based Instance-Transfer Method for Power System Online Transient Stability Assessment [J].
Li, Feng ;
Wang, Qi ;
Tang, Yi ;
Xu, Yan ;
Dang, Jie .
CSEE JOURNAL OF POWER AND ENERGY SYSTEMS, 2024, 10 (04) :1664-1675
[35]   A new power system transient stability assessment method based on Type-2 fuzzy neural network estimation [J].
Sharifian, Amir ;
Sharifian, Saeed .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2015, 64 :71-87