Comparison analysis on damping mechanisms of power systems with induction generator based wind power generation

被引:24
作者
Bu, S. Q. [1 ]
Zhang, X. [2 ]
Zhu, J. B. [3 ]
Liu, X. [4 ]
机构
[1] Hong Kong Polytech Univ, Dept Elect Engn, Kowloon, Hong Kong, Peoples R China
[2] Natl Grid, Wokingham RG41 5BN, England
[3] Tianjin Univ, Sch Elect & Informat Engn, Tianjin, Peoples R China
[4] Queens Univ Belfast, Sch Elect Elect Engn & Comp Sci, Belfast BT9 5AH, Antrim, North Ireland
关键词
Damping torque analysis; DFIG; FSIG; Model transformation; Phillips-Heffron model; Wind power generation; SMALL-SIGNAL STABILITY; INCREASED PENETRATION; WIDE-AREA; OSCILLATION; TURBINE; IMPACT; SPEED; FARMS; MODES; PSS;
D O I
10.1016/j.ijepes.2017.10.029
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The rotor structure varies with different types of wind power induction generator (WPIG), which leads to their different dynamic behaviors during power system disturbances. This paper proposes a generic implementation framework of explicit damping torque analysis to investigate the damping mechanisms of power system integrated with induction generator based wind power generation, so that the essential difference and inner connection between two main types of WPIG (i.e., DFIG and FSIG) in damping power system oscillation can be revealed. The linearized models which can represent DFIG and FSIG as well as three transitional wound rotor generators are established to facilitate the analytical comparison analysis. Phillips-Heffron system linearized model is employed to derive an explicit expression of damping torque contribution from main dynamic components of WPIGs. In the paper, 16-machine 5-area NYPS-NETS example system is used for the demonstration of proposed framework and comparison analysis. Both damping effectiveness and robustness of different WPIGs are extensively examined under multiple operating status, in order to provide useful guidance to system planner for the real-time operation of induction generator based wind generation.
引用
收藏
页码:250 / 261
页数:12
相关论文
共 38 条
  • [1] Analysis and Impacts of Implementing Droop Control in DFIG-Based Wind Turbines on Microgrid/Weak-Grid Stability
    Arani, Mohammadreza F. M.
    Mohamed, Yasser Abdel-Rady I.
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2015, 30 (01) : 385 - 396
  • [2] Implementing Virtual Inertia in DFIG-Based Wind Power Generation
    Arani, Mohammadreza Fakhari Moghaddam
    El-Saadany, Ehab F.
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2013, 28 (02) : 1373 - 1384
  • [3] Coordinating Wind Farms and Battery Management Systems for Inter-Area Oscillation Damping: A Frequency-Domain Approach
    Chandra, Souvik
    Gayme, Dennice F.
    Chakrabortty, Aranya
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2014, 29 (03) : 1454 - 1462
  • [4] CIGRE technical brochure on modeling and dynamic behavior of wind generation as it relates to power system control and dynamic performance Working Group 01 Advisory Group 6 Study Committee C4, 2006, CIGRE TECHN IN PRESS
  • [5] Fan L., 2008, Power and Energy Society General Meeting-Conversion and Delivery of Electrical Energy in the 21st Century, P1
  • [6] Fayek HM, 2014, P 5 INT C INT ADV SY, P1
  • [7] Impact of Tie-Line Power on Inter-Area Modes With Increased Penetration of Wind Power
    Garmroodi, Mehdi
    Hill, David J.
    Verbic, Gregor
    Ma, Jin
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2016, 31 (04) : 3051 - 3059
  • [8] Control Strategy to Mitigate the Impact of Reduced Inertia Due to Doubly Fed Induction Generators on Large Power Systems
    Gautam, Durga
    Goel, Lalit
    Ayyanar, Raja
    Vittal, Vijay
    Harbour, Terry
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2011, 26 (01) : 214 - 224
  • [9] Impact of Increased Penetration of DFIG-Based Wind Turbine Generators on Transient and Small Signal Stability of Power Systems
    Gautam, Durga
    Vittal, Vijay
    Harbour, Terry
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2009, 24 (03) : 1426 - 1434
  • [10] Global wind energy council, GLOB WIND REP ANN MA