A novel hysteresis current controller for active power filter with constant switching frequency

被引:0
作者
Zeng, J [1 ]
Jiao, LW [1 ]
Ni, YX [1 ]
Chen, SS [1 ]
Zhang, BL [1 ]
Shen, CM [1 ]
Wu, FF [1 ]
机构
[1] Tsing Hua Univ, Dept Elect Engn, Beijing 100084, Peoples R China
来源
IPEMC 2000: THIRD INTERNATIONAL POWER ELECTRONICS AND MOTION CONTROL CONFERENCE, VOLS 1-3, PROCEEDINGS | 2000年
关键词
active power filter; hysteresis current controller; optimal voltage space vector;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A novel hysteresis current controller for active power filter (APF) is suggested which is based on optimal voltage vectors and in the meantime with constant switching frequency. In this controller the location region of the reference voltage vector is detected quickly by a set of hysteresis comparators through one trial-and-error process. Two appropriate switches are then selected to control the corresponding two line to line currents independently with constant switching frequency. The new method has the advantages of quick response, good current tracking accuracy, and constant switching frequency. Therefore it is very efficient and secure in operation. Computer simulation results show that the new current control method can improve APF performance noticeably.
引用
收藏
页码:692 / 697
页数:6
相关论文
共 6 条
  • [1] AKAGI H, 1988, 1988 IEEE, P867
  • [2] CURRENT CONTROL OF VSI-PWM INVERTERS
    BROD, DM
    NOVOTNY, DW
    [J]. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1985, 21 (03) : 562 - 570
  • [3] GAO JD, 1983, ELECT MACH TRANSIENT, V1
  • [4] High-performance hysteresis modulation technique for active filters
    Malesani, L
    Mattavelli, P
    Tomasin, P
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 1997, 12 (05) : 876 - 884
  • [5] GUI ENHANCES ELECTROMAGNETIC TRANSIENTS SIMULATION TOOLS
    NAYAK, O
    IRWIN, G
    NEUFELD, A
    [J]. IEEE COMPUTER APPLICATIONS IN POWER, 1995, 8 (01): : 17 - 22
  • [6] ZENG J, IN PRESS IEE P GEN T