Hourly dynamic simulation of solar ejector cooling system using TRNSYS for Jordanian climate

被引:79
作者
Tashtoush, Bourhan [1 ]
Alshare, Aiman [2 ]
Al-Rifai, Saja [1 ]
机构
[1] JUST, Dept Mech Engn, Irbid, Jordan
[2] German Jordanian Univ, Mech & Maintenance Engn Dept, Sakhr Al Ahmasi, Jordan
关键词
Solar cooling air-conditioning; Ejector; Evacuated tube solar collectors; Flat plate collector; TRNSYS; EES; VARIABLE GEOMETRY EJECTORS; REFRIGERATION SYSTEM; PERFORMANCE; DESIGN; COLLECTORS; CYCLES; ENERGY; R600A;
D O I
10.1016/j.enconman.2015.05.010
中图分类号
O414.1 [热力学];
学科分类号
摘要
This work describes a simulation program developed on the TRNSYS-EES softwares. This program is used to design the solar collector subsystem components and to evaluate the performance of the solar ejector cooling system with R134a as a refrigerant. In addition dynamic hourly simulation of 7 kW solar ejector cooling system (SECS) constant pressure mixing components, using TRNSYS software is carried out. The performance of solar collector and the overall system performance are investigated and the ejector sub-system is modeled with EES software. The solar collector type, area, storage tank size, and the flow rate through the cycle are optimized. Solar collector type and area are selected based on the maximum energy gain, where the maximum energy gain is a measure of the collector performance. The system performance is computed in the form of desired outlet temperature to run 7 kW cooling cycle. The effect of tilt angle on the solar system performance is investigated and the optimum tilt angle for the best performance of the system is determined. Selection of the best refrigerant to meet the cooling requirement with the maximum COP is studied. In addition, the time fraction of the storage tank outlet temperature for different collector areas, at a mass flow rate of 50 kg/h m(2) is investigated. It is found that evacuated tube type has better performance than the flat plate type, where each collector is anchored at its optimal tilt angle of 28 degrees. Furthermore, the energy required of the 7 kW-cooling-system is adequately met with the selection of an evacuated-tube solar collector system with an area of 60-70 m(2). The solar fraction is in the range of 0.52-0.542 and the corresponding time fraction is 5.04 h/days. Hourly and monthly simulation of SECS, which is supplemented with 2 m(3) storage tank size and operated at a flow rate of 50 kg/h per square meter of collector area is carried out. Under peak solar radiation and highest ambient temperature, the overall system efficiency has a minimum value of 0.32, whereas the COPejec of the ejector cooling cycle for this model is in the range of 0.52-0.547, the solar collector efficiency is between 0.52 and 0.92, and the overall COPo is in the range of 0.32-0.47. (C) 2015 Elsevier Ltd. All rights reserved.
引用
收藏
页码:288 / 299
页数:12
相关论文
共 37 条
[1]   A solar-driven ejector refrigeration system for Mediterranean climate: Experience improvement and new results performed [J].
Allouche, Yosr ;
Bouden, Chiheb ;
Riffat, Saffa .
TERRAGREEN 2012: CLEAN ENERGY SOLUTIONS FOR SUSTAINABLE ENVIRONMENT (CESSE), 2012, 18 :1115-1124
[2]  
[Anonymous], 2013, TRNSYS 17 TRANSIENT
[3]  
[Anonymous], 1980, SOLAR ENG THERMAL PR
[4]   Modeling of an ejector refrigerating system operating in dimensioning and off-dimensioning conditions with the working fluids R142b and R600a [J].
Boumaraf, Latra ;
Lallemand, Andre .
APPLIED THERMAL ENGINEERING, 2009, 29 (2-3) :265-274
[5]   Design and dynamic simulation of a novel solar trigeneration system based on hybrid photovoltaic/thermal collectors (PVT) [J].
Calise, Francesco ;
d'Accadia, Massimo Dentice ;
Vanoli, Laura .
ENERGY CONVERSION AND MANAGEMENT, 2012, 60 :214-225
[6]   Design and dynamic simulation of a novel polygeneration system fed by vegetable oil and by solar energy [J].
Calise, Francesco ;
Palombo, Adolfo ;
Vanoli, Laura .
ENERGY CONVERSION AND MANAGEMENT, 2012, 60 :204-213
[7]   Design and performance of a solar-powered heating and cooling system using silica gel/water adsorption chiller [J].
Chang, W-S. ;
Wang, C. -C. ;
Shieh, C. -C. .
APPLIED THERMAL ENGINEERING, 2009, 29 (10) :2100-2105
[8]   Modeling of a residential house coupled with a dual source heat pump using TRNSYS software [J].
Chargui, R. ;
Sammouda, H. .
ENERGY CONVERSION AND MANAGEMENT, 2014, 81 :384-399
[9]   Numerical simulation of a cooling tower coupled with heat pump system associated with single house using TRNSYS [J].
Chargui, R. ;
Sammouda, H. ;
Farhat, A. .
ENERGY CONVERSION AND MANAGEMENT, 2013, 75 :105-117
[10]   On the validity of a design method for a solar-assisted ejector cooling system [J].
Colle, S. ;
Pereira, G. S. ;
Vidal Gutierrez, H. R. ;
Escobar Moragas, R. .
SOLAR ENERGY, 2009, 83 (02) :139-149