Evidence updating with static and dynamical performance analyses for industrial alarm system design

被引:25
作者
Xu, Xiaobin [1 ]
Weng, Xu [1 ]
Xu, Dongling [3 ]
Xu, Haiyang [1 ]
Hu, Yanzhu [2 ]
Li, Jianning [1 ]
机构
[1] Hangzhou Dianzi Univ, Sch Automat, Hangzhou 100084, Peoples R China
[2] Beijing Univ Posts & Telecommun, Sch Automat, Beijing 100876, Peoples R China
[3] Univ Manchester, Manchester Business Sch, Manchester M15 6PB, Lancs, England
关键词
Dempster-Shafer theory of evidence; Alarm system design; Information fusion; Epistemic and aleatory uncertainties; Data-driven design;
D O I
10.1016/j.isatra.2019.09.006
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
In the Dempster-Shafer theory (DST) of evidence, the alarm evidence updating-based method can effectively deal with the uncertainty of the monitored process variable so as to significantly reduce the false alarm rates (FAR) and missed alarm rates (MAR) of the industrial alarm system. But the price of the decrease of FAR and MAR is the increase of the averaged alarm delay (AAD). In order to obtain better comprehensive performance, besides the accuracy indices (FAR and MAR), the sensitivity index (AAD) should be considered simultaneously in the alarm system parameter optimization design. In the framework of DST, firstly, this paper defines the static and dynamical performance indices in the alarm evidence space which are compatible with FAR/MAR/AAD in the process variable space. But the former can measure the performance of the DST-based alarm systems more naturally and elaborately than the latter; secondly, a systematic parameter optimization design procedure for the alarm system is investigated by using these new indices and the tradeoff among them. Finally, two typical numerical experiments and an industrial case are provided to illustrate the effectiveness of the static and dynamical indices for improving the comprehensive performance of the DST-based alarm systems. (C) 2019 Published by Elsevier Ltd on behalf of ISA.
引用
收藏
页码:110 / 122
页数:13
相关论文
共 26 条
[1]  
[Anonymous], 2007, EEMUA191
[2]  
[Anonymous], 2009, ANSIISA182
[3]   Fault-tree analysis for liquefied natural gas terminal emergency shutdown system [J].
Cheng, Shuen-Ren ;
Lin, Binshan ;
Hsu, Bi-Min ;
Shu, Ming-Hung .
EXPERT SYSTEMS WITH APPLICATIONS, 2009, 36 (09) :11918-11924
[4]   Optimal Alarm Signal Processing: Filter Design and Performance Analysis [J].
Cheng, Yue ;
Izadi, Iman ;
Chen, Tongwen .
IEEE TRANSACTIONS ON AUTOMATION SCIENCE AND ENGINEERING, 2013, 10 (02) :446-451
[5]   Generalized evidence theory [J].
Deng, Yong .
APPLIED INTELLIGENCE, 2015, 43 (03) :530-543
[6]   Modeling contaminant intrusion in water distribution networks: A new similarity-based DST method [J].
Deng, Yong ;
Jiang, Wen ;
Sadiq, Rehan .
EXPERT SYSTEMS WITH APPLICATIONS, 2011, 38 (01) :571-578
[7]   A correlation consistency based multivariate alarm thresholds optimization approach [J].
Gao, Huihui ;
Liu, Feifei ;
Zhu, Qunxiong .
ISA TRANSACTIONS, 2016, 65 :37-43
[8]  
Izadi I., 2009, P 7 IFAC SAFEPROCESS, P651, DOI [10.3182/20090630-4-ES-2003.00108, DOI 10.3182/20090630-4-ES-2003.00108]
[9]  
Joussleme A.-L., 2001, Information Fusion, V2, P91, DOI 10.1016/S1566-2535(01)00026-4
[10]   Conditioning and updating evidence [J].
Kulasekere, EC ;
Premaratne, K ;
Dewasurendra, DA ;
Shyu, ML ;
Bauer, PH .