Full scale experimental study of single-sided ventilation: Analysis of stack and wind effects

被引:96
作者
Caciolo, Marcello [1 ]
Stabat, Pascal [1 ]
Marchio, Dominique [1 ]
机构
[1] CEP Mines ParisTech, F-75272 Paris 06, France
关键词
Natural ventilation; Single-sided; Free cooling; Window opening; Passive cooling; Full scale experiment; NATURAL VENTILATION; FLOW; DESIGN;
D O I
10.1016/j.enbuild.2011.03.019
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Natural ventilation can contribute to the reduction of the air conditioning demand and to the improvement of thermal comfort in buildings. In this paper, the flow field and the air change rate generated by a simple configuration of natural ventilation, namely single-sided ventilation, are examined experimentally. The experiments are realized in a full scale building exposed to outdoor conditions, using several measurement techniques. The main features of the flow generated by stack and wind effect are examined for different outdoor conditions (temperature difference, wind speed and direction). Finally, measured air change rates are compared to those calculated by existing correlations in order to analyze their applicability to the experimental configuration. Results show that the wind generates turbulence diffusion at the opening, counteracting the stack effect. Moreover, in the case of windward opening, there is an additional effect, namely the effect of mixing layer, which tends to increase the airflow rate. Existing correlations give reasonably good results in the case of windward opening, while in the case of leeward opening they overestimate the airflow rate. (C) 2011 Elsevier B.V. All rights reserved.
引用
收藏
页码:1765 / 1773
页数:9
相关论文
共 17 条
[1]  
ALLARD F., 1998, Natural ventilation in buildings: a design handbook
[2]   Design analysis of single-sided natural ventilation [J].
Allocca, C ;
Chen, QY ;
Glicksman, LR .
ENERGY AND BUILDINGS, 2003, 35 (08) :785-795
[3]  
[Anonymous], 1982, AIR INFILTRATION REV
[4]  
[Anonymous], C P ENERGY CONSERVAT
[5]  
BIENFAIT D, 1991, P 12 AIVC C OTT CAN, V1
[6]  
BROWN WG, 1962, HEAT MASS TRANSFER, V5, P859
[7]  
Caciolo M., 2010, THESIS ECOLE NATL SU
[8]   On the combination of air velocity and flow measurements in single sided natural ventilation configurations [J].
Dascalaki, E ;
Santamouris, M ;
Argiriou, A ;
Helmis, C ;
Asimakopoulos, DN ;
Papadopoulos, K ;
Soilemes, A .
ENERGY AND BUILDINGS, 1996, 24 (02) :155-165
[9]   Unsteady flow effects due to fluctuating wind pressures in natural ventilation design - instantaneous flow rates [J].
Etheridge, DW .
BUILDING AND ENVIRONMENT, 2000, 35 (04) :321-337
[10]  
Feustel V., 2001, COMIS 3 1 USERS GUID