Quantification of corona discharges on nonceramic insulators

被引:56
作者
Pinnangudi, B [1 ]
Gorur, RS
Kroese, AJ
机构
[1] Arizona State Univ, Dept Elect Engn, Tempe, AZ 85287 USA
[2] Salt River Project, Phoenix, AZ USA
关键词
insulators; hydrophobicity; partial discharge; corona; field inspection; image processing;
D O I
10.1109/TDEI.2005.1453456
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper attempts to establish a correlation of the visual images of corona obtained from a camera with discharge magnitude measured with conventional partial discharge equipment. A linear relationship is shown between the transformed image parameters and the discharge magnitude, thereby providing a means for quantifying corona observations made during routine maintenance inspections of insulators from ground. Different insulator designs using silicone rubber (SIR) and ethylene propylene diamene monomer (EPDM) housings were examined. The effect of fog has been examined by performing experiments inside a fog chamber. It is shown that this information can be used along with the corona degradation characteristics of housing materials to identify discharge patterns that can pose problems to the integrity of the insulator.
引用
收藏
页码:513 / 523
页数:11
相关论文
共 18 条
[1]   Computer-aided reconstruction of cathode images obtained by high speed photography of high current vacuum arcs [J].
Afanas'ev, VP ;
Chaly, AM ;
Logatchev, AA ;
Shkol'nik, SM ;
Zabello, KK .
IEEE TRANSACTIONS ON PLASMA SCIENCE, 2001, 29 (05) :695-699
[2]   STREAK PHOTOGRAPHY OF THE DYNAMIC-ELECTRICAL DISCHARGE BEHAVIOR ON INSULATOR SURFACES IN VACUUM [J].
ASOKAN, T ;
SUDARSHAN, TS .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1993, 28 (01) :101-110
[3]   PRE-FLASHOVER LUMINOSITY ALONG AN ALUMINA VACUUM INTERFACE [J].
ASOKAN, T ;
SUDARSHAN, TS .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1994, 1 (06) :1180-1185
[4]   HIGH-SPEED PHOTOGRAPHY OF SURFACE FLASHOVER ACROSS HIGH-DENSITY ALUMINA IN VACUUM UNDER DIRECT AND IMPULSE VOLTAGES [J].
CROSS, JD ;
SUDARSHAN, TS .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1976, 11 (02) :63-66
[5]  
DYOGO G, 1993, IEEE T PLASMA SCI, V21, P407
[6]  
Gorur R. S., 1999, Outdoor insulators
[7]   Production of chemically active species in the air by a single positive streamer in a nonuniform field [J].
Kulikovsky, AA .
IEEE TRANSACTIONS ON PLASMA SCIENCE, 1997, 25 (03) :439-446
[8]   CHARACTERISTICS OF PREFLASHOVER LIGHT-EMISSION FROM DIELECTRIC SURFACES IN VACUUM [J].
LI, CR ;
SUDARSHAN, TS .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1995, 2 (03) :483-491
[9]   Mechanism of brittle fracture in nonceramic insulators [J].
Montesinos, J ;
Gorur, RS ;
Mobasher, B ;
Kingsbury, D .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2002, 9 (02) :236-243
[10]   Impact of corona on the long-term performance of nonceramic insulators [J].
Moreno, VM ;
Gorur, RS ;
Kroese, A .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2003, 10 (01) :80-95