Variable evaporating temperature control strategy for VRV system under part load conditions in cooling mode

被引:44
作者
Zhao, Deyin [1 ]
Zhang, Xu [1 ]
Zhong, Ming [1 ,2 ]
机构
[1] Tongji Univ, Inst HVAC&Gas Engn, Shanghai 200092, Peoples R China
[2] Daikin China Investment Co Ltd, Shanghai, Peoples R China
关键词
VRV; Variable evaporating temperature; Part load condition; Control strategy; REFRIGERANT-FLOW SYSTEMS; FIELD PERFORMANCE-MEASUREMENTS; PUMP DESICCANT SYSTEMS; ENERGY SIMULATION; INTEGRATION; VOLUME; UNIT;
D O I
10.1016/j.enbuild.2015.01.039
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Control strategy is key technology for efficient and reliable operation of air conditioning system. Although VRV research is booming in recent years, the general control strategy of VRV system is still to regulate refrigerant flow rate while keeping evaporating temperature or discharge pressure constant during cooling or heating process. In this paper, a novel control strategy with variable evaporating temperature is explored under part load conditions. Based on running point determined by original control strategy, the new strategy further reduces running frequency under the same part load conditions. Correspondingly, energy consumption reduces and evaporating temperature rises. Theoretical analysis proves its feasibility of energy saving. Further experimental results show that the novel control strategy would help to improve VRV system energy efficiency and reduce cooling energy consumption especially for part load conditions lower than 50%. (C) 2015 Elsevier B.V. All rights reserved.
引用
收藏
页码:180 / 186
页数:7
相关论文
共 29 条
  • [1] Amamath A., 2008, Engineered Systems, V25, P54
  • [2] [Anonymous], 2006, DES INST TEST INSTR
  • [3] [Anonymous], COMM AIR COND MARK R
  • [4] [Anonymous], 2014, ANNUAL REPORT CHINA
  • [5] Field performance measurements of a heat pump desiccant unit in dehumidification mode
    Aynur, T. N.
    Hwang, Y. H.
    Radermacher, R.
    [J]. ENERGY AND BUILDINGS, 2008, 40 (12) : 2141 - 2147
  • [6] Aynur T. N., 2006, 11 INT REFR AIR COND
  • [7] Integration of variable refrigerant flow and heat pump desiccant systems for the heating season
    Aynur, Toga N.
    Hwang, Yunho
    Radermacher, Reinhard
    [J]. ENERGY AND BUILDINGS, 2010, 42 (04) : 468 - 476
  • [8] Variable refrigerant flow systems: A review
    Aynur, Tolga N.
    [J]. ENERGY AND BUILDINGS, 2010, 42 (07) : 1106 - 1112
  • [9] Integration of variable refrigerant flow and heat pump desiccant systems for the cooling season
    Aynur, Tolga N.
    Hwang, Yunho
    Radermacher, Reinhard
    [J]. APPLIED THERMAL ENGINEERING, 2010, 30 (8-9) : 917 - 927
  • [10] Simulation comparison of VAV and VRF air conditioning systems in an existing building for the cooling season
    Aynur, Tolga N.
    Hwang, Yunho
    Radermacher, Reinhard
    [J]. ENERGY AND BUILDINGS, 2009, 41 (11) : 1143 - 1150