Coordinated hierarchical voltage control for flexible DC distribution systems

被引:2
作者
Wei, Zhiyu [1 ]
Peng, Ke [1 ]
Xiao, Chuanliang [1 ]
Li, Yan [2 ]
Zhao, Xueshen [3 ]
Yao, Guangzeng [1 ]
机构
[1] Shandong Univ Technol, Sch Elect & Elect Engn, Xincun West Rd 266, Zibo, Peoples R China
[2] Penn State Univ, Dept Elect Engn, University Pk, PA 16802 USA
[3] Tianjin Univ, Key Lab Smart Grid, Minist Educ, Weijin Rd 92, Tianjin, Peoples R China
关键词
Flexible DC distribution systems; Dynamic performance; Steady-state performance; Coordinated hierarchical voltage control; (CHVC); DROOP CONTROL; STRATEGY;
D O I
10.1016/j.epsr.2021.107572
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The poor voltage stability and weak damping of flexible DC distribution system bring great challenges to its safe and stable operation, and its power imbalance also has a negative impact on AC distribution system. In this paper, a novel dead-zone based PID control strategy and a coordinated hierarchical voltage control (CHVC) paradigm are presented to improve the voltage stability and the damping of flexible DC distribution systems. The dead-zone based PID control is performed by a PID controller with a dead zone. It can not only carry out fast power demand response, but also prolong the service life of the battery. The CHVC strategy coordinates the battery converter control and the interconnected voltage source converter (VSC) droop control. It can not only improve the overall dynamic and steady-state characteristics of the system, but also reduce the influence of the DC system unbalanced power on the AC system. Furthermore, the effects of DC line parameters, the intensity of interconnected AC distribution systems and outer loop control parameters on the stability of the system are also analyzed, which can provide a theoretical basis for the selection of system hardware and control parameters. Numerical examples verify the feasibility and the effectiveness of CHVC.
引用
收藏
页数:9
相关论文
共 23 条
  • [1] Investigation of Nonlinear Droop Control in DC Power Distribution Systems: Load Sharing, Voltage Regulation, Efficiency, and Stability
    Chen, Fang
    Burgos, Rolando
    Boroyevich, Dushan
    Vasquez, Juan C.
    Guerrero, Josep M.
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 2019, 34 (10) : 9404 - 9421
  • [2] Grillo S., 2012, 2012 IEEE 15 INT C H
  • [3] Hatahet W., INT J ELEC POWER, V130, P3032
  • [4] Jing G., 2019, 2019 CHIN CONTR DEC
  • [5] Voltage Regulation Method for Voltage Drop Compensation and Unbalance Reduction in Bipolar Low-Voltage DC Distribution System
    Jung, Tack-Hyun
    Gwon, Gi-Hyeon
    Kim, Chul-Hwan
    Han, Joon
    Oh, Yun-Sik
    Noh, Chul-Ho
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (01) : 141 - 149
  • [6] King James, 2017, CIRED - Open Access Proceedings Journal, V2017, P445, DOI 10.1049/oap-cired.2017.0941
  • [7] Krishan R, 2017, 2017 IEEE INTERNATIONAL CONFERENCE ON SMART GRID AND SMART CITIES (ICSGSC), P146, DOI 10.1109/ICSGSC.2017.8038566
  • [8] Sixth harmonic-based fault location for VSC-DC distribution systems
    Li, Meng
    Jia, Ke
    Bi, Tianshu
    Yang, Qixun
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2017, 11 (14) : 3485 - 3490
  • [9] Li XY, 2017, J ENG-JOE
  • [10] A novel droop control method based on virtual frequency in DC microgrid
    Liu, Yancheng
    Zhuang, Xuzhou
    Zhang, Qinjin
    Arslan, Muhammad
    Guo, Haohao
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2020, 119 (119)