Breakdown Strength of Vegetable-based Oils Under AC and Lightning Impulse Voltages

被引:0
作者
Vukovic, Dejan [1 ]
Tenbohlen, Stefan [1 ]
Harthun, Joerg [2 ]
Perrier, Christophe [3 ]
Fink, Harald [4 ]
机构
[1] Univ Stuttgart, Inst Power Transmiss & High Voltage Technol, Stuttgart, Germany
[2] Alstom Grid, Engn, Monchengladbach, Germany
[3] Alstom Grid, Technol Innovat & Competence Dev Ctr TICC, Massy, France
[4] Alstom Grid, R&D Competence Ctr, Monchengladbach, Germany
来源
2011 IEEE INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS (ICDL) | 2011年
关键词
Vegetable-based oil; mineral oil; breakdown voltage; power transformers;
D O I
暂无
中图分类号
O69 [应用化学];
学科分类号
081704 ;
摘要
The breakdown strength of vegetable-based oil (VBO) and mineral oil is compared by means of experimental determination of breakdown voltage. These oils were tested under AC and positive lightning impulse voltages for uniform and non-uniform electrical field. The oil gap varied from 2 mm up to 85 mm. The results show same or higher AC breakdown strength of VBO compared to mineral oil for small gaps and uniform electrical field, whereas for lightning impulses and non-uniform field breakdown strength of VBO is reduced.
引用
收藏
页数:4
相关论文
共 5 条
[1]   Streamer Propagation and Breakdown in Natural Ester at High Voltage [J].
Duy, C. Tran ;
Lesaint, O. ;
Denat, A. ;
Bonifaci, N. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2009, 16 (06) :1582-1594
[2]  
Rapp K. J., 2010, 2010 International Conference on High Voltage Engineering and Application (ICHVE 2010), P104, DOI 10.1109/ICHVE.2010.5640853
[3]  
Tenbohlen S., CIGRE SESS 2008 PAR
[4]   Prediction of breakdown voltage of transformer oil from predischarge phenomena [J].
Torshin, YV .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2003, 10 (06) :933-941
[5]  
Viet-Hung Dang, 2010, 2010 International Conference on High Voltage Engineering and Application (ICHVE 2010), P560, DOI 10.1109/ICHVE.2010.5640765