Assessment of State-Space Building Energy System Models in Terms of Stability and Controllability

被引:3
作者
Harish, V. S. K. V. [1 ]
Kumar, Arun [2 ]
Alam, Tabish [3 ]
Blecich, Paolo [4 ]
机构
[1] Netaji Subhas Univ Technol NSUT, Dept Elect Engn, Sect 3, Delhi 110078, India
[2] Indian Inst Technol Roorkee IITR, Dept Hydro & Renewable Energy, Roorkee 247667, Uttar Pradesh, India
[3] CSIR Cent Bldg Res Inst, Roorkee 247667, Uttar Pradesh, India
[4] Univ Rijeka, Fac Engn, Dept Thermodynam & Energy Engn, Rijeka 51000, Croatia
关键词
building energy systems; modeling and simulation; stability assessment; controllability; multi-input multi-output system; THERMAL COMFORT; OPTIMIZATION; IDENTIFICATION; PERFORMANCE; SIMULATION; EFFICIENCY; DESIGN;
D O I
10.3390/su132111938
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Building energy management system involves the development of control strategies for the heating, ventilation, and air-conditioning (HVAC), as well as lighting, systems. Building energy modeling is a significant part of designing such strategies. In order to analyze the feasibility of a building energy system model for any desired control strategy, a mathematical assessment tool is developed in this paper. A multi-input multi-output (MIMO) building energy system model, consisting of an outdoor wall, an external wall, two partition walls, one roof, and a ceiling, has been considered as the virtual test setup. A methodology for conducting stability and controllability assessment tests on the building energy model is proposed using inverse dynamics input theory (IDIT). IDIT enables the decoupling of control variables so as to enable the conversion of an MIMO system to a number of independent single-input single-output systems. The controllability is assessed based on the design properties for continuous systems: asymptotes and transmission zeros. The results show that the relative humidity and air temperature of the building space were controllable for all operating points; however, in unconditioned situations, where the humidity levels of the building space were greater than that of the outdoor levels, the models were unstable.
引用
收藏
页数:26
相关论文
共 50 条
  • [1] [Anonymous], 2010, 1402007 ANSIASHRAE
  • [2] Experimental and numerical thermal performance assessment of a multi-layer building envelope component made of biocomposite materials
    Arregi, Benat
    Garay-Martinez, Roberto
    Astudillo, Julen
    Garcia, Miriam
    Carlos Ramos, Juan
    [J]. ENERGY AND BUILDINGS, 2020, 214 (214)
  • [3] A real industrial building: Modeling, calibration and Pareto optimization of energy retrofit
    Ascione, Fabrizio
    Bianco, Nicola
    Iovane, Teresa
    Mauro, Gerardo Maria
    Napolitano, Davide Ferdinando
    Ruggiano, Antonio
    Viscido, Lucio
    [J]. JOURNAL OF BUILDING ENGINEERING, 2020, 29
  • [4] Can whole building energy models outperform numerical models, when forecasting performance of indirect evaporative cooling systems?
    Badiei, A.
    Akhlaghi, Y. G.
    Zhao, X.
    Li, J.
    Yi, F.
    Wang, Z.
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2020, 213
  • [5] Experimental demonstration of data predictive control for energy optimization and thermal comfort in buildings
    Buenning, Felix
    Huber, Benjamin
    Heer, Philipp
    Aboudonia, Ahmed
    Lygeros, John
    [J]. ENERGY AND BUILDINGS, 2020, 211
  • [6] Campisi D., 2018, INT J ENERGY EC POLI, V8, P185
  • [7] BIM-Based Energy Analysis and Sustainability Assessment-Application to Portuguese Buildings
    Carvalho, Jose Pedro
    Almeida, Manuela
    Braganca, Luis
    Mateus, Ricardo
    [J]. BUILDINGS, 2021, 11 (06)
  • [8] Counsell J.M., 2008, P 10 WORLD REN EN C
  • [9] Counsell J.M., 2011, P CIBSE TECHN S LEIC
  • [10] Controllability of buildings: A multi-input multi-output stability assessment method for buildings with slow acting heating systems
    Counsell, John M.
    Khalid, Yousaf A.
    Brindley, Joseph
    [J]. SIMULATION MODELLING PRACTICE AND THEORY, 2011, 19 (04) : 1185 - 1200