Numerical and experimental study on biased tube temperature problem in tangential firing boiler

被引:15
作者
Akkinepally, Bhargav [1 ]
Shim, Jaesool [1 ]
Yoo, Kisoo [1 ]
机构
[1] Yeungnam Univ, Sch Mech Engn, Gyongsan, Gyeonsanbukdo, South Korea
基金
新加坡国家研究基金会;
关键词
Tangential firing boiler; Tube temperature; CFD; Residual swirl; PULVERIZED-COAL BOILER; UTILITY BOILER; POWER-GENERATION; FIRED BOILERS; HEAT-TRANSFER; COMBUSTION; FLOW; FURNACE; EMISSIONS;
D O I
10.1016/j.applthermaleng.2017.07.121
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this study, a numerical and experimental investigation on the flow field in a 500-MW unit of a tangentially fired boiler has been performed to understand the effect of residual swirl on the temperature distribution and inconsistency of flow velocity in the crossover pass. The k-k(L)-omega turbulence model was used in this study to analyse the possible formation of transition flow in the tangential firing boiler. Furthermore, 1D and 3D hybrid modelling were used for the simulation of the convective heat transfer in the boiler tube assembly. The commercially available code ANSYS Fluent and COMSOL were used for the studies, respectively. The numerical results for the velocity profile and residual swirl in the boiler were validated using the experimental results from the cold air velocity test, in which the flow velocity was directly measured in the full-scale boiler. The computational results agreed well with the experimental findings. Furthermore, from a comparison of the simulation and experiment, it was found that the biased gas flow induces non-uniform tube temperatures at the crossover pass area of the tangential firing boiler. These results aid in the detailed study of the residual swirl effects on the temperature or flue gas at various locations of the boiler. This study indicates that a non-uniform tube temperature at the crossover pass is an inherent problem resulting from residual swirl in the tangential firing boiler. Therefore, the pulverised coal burner should be fine-tuned to avoid tube rupture due to local overheating. (C) 2017 Elsevier Ltd. All rights reserved.
引用
收藏
页码:92 / 99
页数:8
相关论文
共 19 条
[1]  
[Anonymous], 2014, IEA WORLD ENERGY STA
[2]   Combustion technology developments in power generation in response to environmental challenges [J].
Beér, JM .
PROGRESS IN ENERGY AND COMBUSTION SCIENCE, 2000, 26 (4-6) :301-327
[3]  
Bejan A., 2013, Convective heat transfer
[4]   A numerical study of a utility boiler tangentially-fired furnace under different operating conditions [J].
Belosevic, Srdjan ;
Sijercic, Miroslav ;
Tucakovic, Dragan ;
Crnomarkovic, Nenad .
FUEL, 2008, 87 (15-16) :3331-3338
[5]   Three-dimensional modeling of utility boiler pulverized coal tangentially fired furnace [J].
Belosevic, Srdjan ;
Sijercic, Miroslav ;
Oka, Simeon ;
Tucakovic, Dragan .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2006, 49 (19-20) :3371-3378
[6]   Numerical investigation on the flow, combustion and NOx emission characteristics in a 500 MWe tangentially fired pulverized-coal boiler [J].
Choi, Choeng Ryul ;
Kim, Chang Nyung .
FUEL, 2009, 88 (09) :1720-1731
[7]   Numerical investigation of NOx emissions from a tangentially-fired utility boiler under conventional and overfire air operation [J].
Diez, Luis I. ;
Cortes, Cristobal ;
Pallares, Javier .
FUEL, 2008, 87 (07) :1259-1269
[8]  
Doolye R. B., 2004, 1010542 EPRI
[9]   Components, formulations, solutions, evaluation, and application of comprehensive combustion models [J].
Eaton, AM ;
Smoot, LD ;
Hill, SC ;
Eatough, CN .
PROGRESS IN ENERGY AND COMBUSTION SCIENCE, 1999, 25 (04) :387-436
[10]   Computational modeling of pulverized coal combustion processes in tangentially fired furnaces [J].
Fan, JR ;
Qian, LG ;
Ma, YL ;
Sun, P ;
Cen, KF .
CHEMICAL ENGINEERING JOURNAL, 2001, 81 (1-3) :261-269