Sensitivity analysis of predicted night cooling performance to internal convective heat transfer modelling

被引:37
作者
Goethals, Kim [1 ]
Breesch, Hilde [2 ]
Janssens, Arnold [1 ]
机构
[1] Univ Ghent, Res Grp Bldg Phys Construct & Serv, Dept Architecture & Urban Planning, Fac Engn, B-9000 Ghent, Belgium
[2] Catholic Univ, Coll Ghent, Dept Construct, Sustainable Bldg Res Grp, B-9000 Ghent, Belgium
关键词
Building energy simulation; Internal convective heat transfer; Night cooling; Sensitivity analysis; BUILDING PERFORMANCE; MIXED CONVECTION; INDOOR; VENTILATION; SURFACES; COMFORT; ENERGY;
D O I
10.1016/j.enbuild.2011.05.033
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The potential of night cooling, a passive cooling technique of growing interest, is typically investigated by numerical means. In particular multi-zone energy simulation is currently appraised for building design. Unfortunately, in addition to the inaccurate approximation of an ideally mixed room, the implemented empirical convective heat transfer coefficients (CHTCs) only apply to specific flow regimes - forcing to use arbitrary correlations and, thus, possibly limiting the usefulness of the simulation results. Therefore, the authors of this paper investigate the sensitivity of the night cooling performance to convection algorithms. First, the authors examine the applicability of convection correlations for real building enclosures. extracted from literature. Subsequently, simulations of a night cooled office room during summertime of a moderate climate (Belgium) are carried out in TRNSYS, using different convection correlations in addition to varying design parameters. The results show that the choice of the convection algorithm strongly affects the energy and thermal comfort predictions. More importantly, the convection algorithm is of the same importance as the design parameters - making an exact definition of the CHTC crucial. Therefore. additional research by experiments or airflow codes, based on fluid dynamics, is regarded necessary. (C) 2011 Elsevier B.V. All rights reserved.
引用
收藏
页码:2429 / 2441
页数:13
相关论文
共 39 条
[11]   Performance evaluation of passive cooling in office buildings based on uncertainty and sensitivity analysis [J].
Breesch, H. ;
Janssens, A. .
SOLAR ENERGY, 2010, 84 (08) :1453-1467
[12]  
Breesch H., 2006, Natural night ventilation in office buildings: performance evaluation based on simulation, uncertainty and sensitivity analysis
[13]  
Bureau voor Normalisatie NBN, 2008, B62002 NBN
[14]   GENERAL EXPRESSION FOR CORRELATION OF RATES OF TRANSFER AND OTHER PHENOMENA [J].
CHURCHILL, SW ;
USAGI, R .
AICHE JOURNAL, 1972, 18 (06) :1121-+
[15]   Assessing energy, lighting, room acoustics, occupant comfort and environmental impacts performance of building with a single simulation program [J].
Citherlet, S ;
Hand, J .
BUILDING AND ENVIRONMENT, 2002, 37 (8-9) :845-856
[16]  
Clarke J.A., 1991, Internal convective heat transfer coefficient: A sensitivity study
[17]  
Fisher D.E., 1997, ASHRAE Transactions, V103, P137
[18]  
Fisher D.E., 1995, EXPT INVESTIGATION M
[19]   Effectiveness of mass and night ventilation in lowering the indoor daytime temperatures. Part I: 1993 experimental periods [J].
Givoni, B .
ENERGY AND BUILDINGS, 1998, 28 (01) :25-32
[20]  
Hoseggen R.Z., 2007, DYNAMIC USE BUILDING