Sensitivity analysis of predicted night cooling performance to internal convective heat transfer modelling

被引:37
作者
Goethals, Kim [1 ]
Breesch, Hilde [2 ]
Janssens, Arnold [1 ]
机构
[1] Univ Ghent, Res Grp Bldg Phys Construct & Serv, Dept Architecture & Urban Planning, Fac Engn, B-9000 Ghent, Belgium
[2] Catholic Univ, Coll Ghent, Dept Construct, Sustainable Bldg Res Grp, B-9000 Ghent, Belgium
关键词
Building energy simulation; Internal convective heat transfer; Night cooling; Sensitivity analysis; BUILDING PERFORMANCE; MIXED CONVECTION; INDOOR; VENTILATION; SURFACES; COMFORT; ENERGY;
D O I
10.1016/j.enbuild.2011.05.033
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The potential of night cooling, a passive cooling technique of growing interest, is typically investigated by numerical means. In particular multi-zone energy simulation is currently appraised for building design. Unfortunately, in addition to the inaccurate approximation of an ideally mixed room, the implemented empirical convective heat transfer coefficients (CHTCs) only apply to specific flow regimes - forcing to use arbitrary correlations and, thus, possibly limiting the usefulness of the simulation results. Therefore, the authors of this paper investigate the sensitivity of the night cooling performance to convection algorithms. First, the authors examine the applicability of convection correlations for real building enclosures. extracted from literature. Subsequently, simulations of a night cooled office room during summertime of a moderate climate (Belgium) are carried out in TRNSYS, using different convection correlations in addition to varying design parameters. The results show that the choice of the convection algorithm strongly affects the energy and thermal comfort predictions. More importantly, the convection algorithm is of the same importance as the design parameters - making an exact definition of the CHTC crucial. Therefore. additional research by experiments or airflow codes, based on fluid dynamics, is regarded necessary. (C) 2011 Elsevier B.V. All rights reserved.
引用
收藏
页码:2429 / 2441
页数:13
相关论文
共 39 条
[1]  
Alamdari F., 1983, BUILD SERV ENG RES T, V4, P106
[2]  
[Anonymous], 2000, ADAPTIVE COUPLING HE
[3]  
[Anonymous], 2009, ASHRAE Handbook|Fundamentals
[4]  
Arnold P., 1998, P ASME HEAT TRANSFER, V361, P47
[5]   Parameter study on performance of building cooling by night-time ventilation [J].
Artmann, N. ;
Manz, H. ;
Heiselberg, P. .
RENEWABLE ENERGY, 2008, 33 (12) :2589-2598
[6]   Natural convection from heated room surfaces [J].
Awbi, HB ;
Hatton, A .
ENERGY AND BUILDINGS, 1999, 30 (03) :233-244
[7]   Mixed convection from heated room surfaces [J].
Awbi, HB ;
Hatton, A .
ENERGY AND BUILDINGS, 2000, 32 (02) :153-166
[8]  
BBRI, 1999, INS VENT HEAT NEWL B
[9]  
Bejan A., 1993, HEAT TRANSFER
[10]   Night ventilation for building cooling in summer [J].
Blondeau, P ;
Sperandio, M ;
Allard, F .
SOLAR ENERGY, 1997, 61 (05) :327-335