Energy consumption of subway stations in China: Data and influencing factors

被引:43
作者
Guan, Bowen [1 ]
Liu, Xiaohua [1 ]
Zhang, Tao [1 ]
Xia, Jianjun [1 ]
机构
[1] Tsinghua Univ, Dept Bldg Sci, Beijing 100084, Peoples R China
基金
中国国家自然科学基金;
关键词
Energy consumption; Statistic analysis; Influencing factors; Subway stations; POWER-CONSUMPTION; SYSTEM;
D O I
10.1016/j.scs.2018.09.018
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Subway transportation systems are in rapid development and energy consumption in subway stations is becoming more and more significant. The present paper aims to reveal the electricity consumption of subway stations for non-traction purpose, and data from 341 subway stations in 5 cities in different climate zones in China have been statistically integrated and analyzed. The results demonstrate that the average annual electricity consumption ranges 1.8-2.3 million kWh in underground non-transfer stations. Electricity consumption per unit floor area is taken as the benchmark to evaluate the energy performance with an annual average value of 131-144 kWh/m(2) in each city. The VAC (ventilation and air conditioning) system and lighting system are found in dominant positions of the total electricity consumption, accounting for about 46% and 27% respectively in City A. Influencing factors of the energy consumption are also analyzed, including floor area, annual passengers, CDD (cooling degree days), service year, PSD (platform screen door) system, platform type and number of entrances. These factors are compared and classified into three categories according to the degree of influence on energy consumption. The current information provides references for understanding the energy consumption level and establishing energy consumption standards for subway stations.
引用
收藏
页码:451 / 461
页数:11
相关论文
共 34 条
[1]  
[Anonymous], MAXIMIZING POTENTIAL
[2]   Energy conservation potential, HVAC installations and operational issues in Hellenic airports [J].
Balaras, CA ;
Dascalaki, E ;
Gaglia, A ;
Droutsa, K .
ENERGY AND BUILDINGS, 2003, 35 (11) :1105-1120
[3]   A breakdown of energy consumption in an underground station [J].
Casals, Miquel ;
Gangolells, Marta ;
Forcada, Nuria ;
Macarulla, Marcel ;
Giretti, Alberto .
ENERGY AND BUILDINGS, 2014, 78 :89-97
[4]  
China Association of Subways, ANN STAT AN URB RAIL
[5]  
Fu K., 2009, Journal of Sustainable Development, V2, P117
[6]   A multi-objective train scheduling model and solution [J].
Ghoseiri, K ;
Szidarovszky, F ;
Asgharpour, MJ .
TRANSPORTATION RESEARCH PART B-METHODOLOGICAL, 2004, 38 (10) :927-952
[7]   Effect of platform screen doors on the indoor air environment of an underground subway station [J].
Han, Hwataik ;
Lee, Jun-Yong ;
Jang, Kyung-Jin .
INDOOR AND BUILT ENVIRONMENT, 2015, 24 (05) :672-681
[8]   A study on the energy consumption unit of subway stations in Korea [J].
Hong, WW ;
Kim, S .
BUILDING AND ENVIRONMENT, 2004, 39 (12) :1497-1503
[9]   Modeling global residential sector energy demand for heating and air conditioning in the context of climate change [J].
Isaac, Morna ;
van Vuuren, Detlef P. .
ENERGY POLICY, 2009, 37 (02) :507-521
[10]  
Kobe Traffic Bureau, 2004, TEST RES REP EN CONS