Primary energy savings in desiccant and evaporative cooling-assisted 100% outdoor air system combined with a fuel cell

被引:26
作者
Kim, Min-Hwi [1 ]
Dong, Hae-Won [1 ]
Park, Joon-Young [1 ]
Jeong, Jae-Weon [1 ]
机构
[1] Hanyang Univ, Coll Engn, Dept Architectural Engn, 222 Wangsimni Ro, Seoul 04763, South Korea
基金
新加坡国家研究基金会;
关键词
Desiccant cooling; Evaporative cooling; Liquid desiccant; 100% outdoor air system; PEMFC; BUILDING COGENERATION APPLICATIONS; LIQUID DESICCANT; TRIGENERATION SYSTEM; COMBINED HEAT; PERFORMANCE ANALYSIS; ABSORPTION CHILLER; POWER PLANTS; DEHUMIDIFICATION; EFFICIENCY; TURBINE;
D O I
10.1016/j.apenergy.2016.08.004
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The main purpose of this study involved investigating the primary energy saving potential of a liquid desiccantand evaporative cooling-assisted 100% outdoor air system (LD-IDECOAS) integrated with a proton exchange membrane fuel cell (PEMFC). During the cooling season, the heat produced by the PEMFC was used to regenerate a weak desiccant solution, and the electricity generated was used to operate the LD-IDECOAS. A pilot LD-IDECOAS powered by a PEMFC was installed and operated in an office space to experimentally verify the annual operating energy savings of the proposed system. The findings indicated that the heat reclaimed from the PEMFC saved 42% of the desiccant solution regenerating energy when compared to that in the case of a conventional gas-fired water heater. The results also suggested that the LD-IDECOAS combined with a PEMFC consumed 21% less primary energy when compared with that of a system powered by grid electricity and a conventional gas-fired water heater. (C) 2016 Elsevier Ltd. All rights reserved.
引用
收藏
页码:446 / 456
页数:11
相关论文
共 43 条
  • [1] Annual evaluation of energy, environmental and economic performances of a membrane liquid desiccant air conditioning system with/without ERV
    Abdel-Salam, Ahmed H.
    Simonson, Carey J.
    [J]. APPLIED ENERGY, 2014, 116 : 134 - 148
  • [2] AEA, 2014, 2014 REF RECOMMENDAT
  • [3] Trigeneration: A comprehensive review based on prime movers
    Al-Sulaiman, Fahad A.
    Hamdullahpur, Feridun
    Dincer, Ibrahim
    [J]. INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2011, 35 (03) : 233 - 258
  • [4] Energy analysis of a trigeneration plant based on solid oxide fuel cell and organic Rankine cycle
    Al-Sulaiman, Fahad A.
    Dincer, Ibrahim
    Hamdullahpur, Feridun
    [J]. INTERNATIONAL JOURNAL OF HYDROGEN ENERGY, 2010, 35 (10) : 5104 - 5113
  • [5] [Anonymous], 2010, ASHRAE GUIDELINE ENG
  • [6] [Anonymous], 2013, ASHRAE
  • [7] Optimized solar-powered liquid desiccant system to supply building fresh water and cooling needs
    Audah, N.
    Ghaddar, N.
    Ghali, K.
    [J]. APPLIED ENERGY, 2011, 88 (11) : 3726 - 3736
  • [8] Exergetic performance analysis of a PEM fuel cell
    Ay, M
    Midilli, A
    Dincer, I
    [J]. INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2006, 30 (05) : 307 - 321
  • [9] Status and development of PEM fuel cell technology
    Barbir, F.
    Yazici, S.
    [J]. INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2008, 32 (05) : 369 - 378
  • [10] Barbir F, 2005, PEMFCS THEORY PRACTI