Comparison of on-line and off-line PD analysis on stator insulation of turbogenerators

被引:0
作者
Zondervan, JP [1 ]
Gulski, E [1 ]
Smit, JJ [1 ]
Krieg-Wezelenburg, MG [1 ]
机构
[1] Delft Univ Technol, High Voltage Lab, Delft, Netherlands
来源
CONFERENCE RECORD OF THE 1998 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, VOLS 1 AND 2 | 1998年
关键词
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this contribution, results of PD pattern analysis of different defects in the stator insulation for different detection methods are discussed. Samples of complete stator windings with intentionally introduced defects have been used for this purpose. The PD signals have been detected and analyzed in two ways: 1. Using the conventional Po detection technique according to IEC 270 recommendation. 2. Using the VHF detection technique apt for on-line measurements. Rogowski coils and stator slot couplers in combination with a spectrum analyzer have been used to measure the VHF response of PD signals.