Longitudinal AC Breakdown Voltage of XLPE-XLPE Interfaces Considering Surface Roughness and Pressure

被引:43
作者
Kantar, Emre [1 ]
Mauseth, Frank [1 ]
Ildstad, Erling [1 ]
Hvidsten, Sverre [2 ]
机构
[1] Norwegian Univ Sci & Technol, Dept Elect Power Engn, N-7491 Trondheim, Norway
[2] SINTEF Energy Res, Dept Elect Power Technol, N-7465 Trondheim, Norway
关键词
Breakdown; cable connector; cable joint; dielectric; interface; interfacial pressure; surface breakdown; surface roughness; tracking failure; XLPE; SOLID-SOLID INTERFACES; STRENGTH; RUBBER; CONTACT;
D O I
10.1109/TDEI.2017.006540
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The interfacial breakdown between two dielectric surfaces has been reported to represent one of the principal causes of failure for power cable joints and connectors; thus, a better understanding of interfacial breakdown mechanisms is vital. The primary purpose of this paper is to investigate the influence of the surface roughness and interfacial pressure on the tangential AC breakdown strength (BDS) of solid-solid interfaces experimentally. The three-dimensional surface texture parameters are utilized to characterize the morphology of the surfaces. Experiments were performed using samples made of cross-linked polyethylene (XLPE) at three different contact pressures. The surface roughness was varied by polishing the surfaces using four different sandpapers of different roughness. Each surface topography was then assessed using a 3-D optical profilometer. Next, the samples were assembled under ambient laboratory conditions. The experimental results showed a good correlation between the tangential BDS and the surface roughness. The results suggested that reducing the surface roughness resulted in decreased mean height of the surface asperities by nearly 97% and increased the real contact area of the interface considerably. As a result, the tangential BDS rose by a factor of 1.85 - 2.15 with increasing pressure. Likewise, the increased contact pressure yielded augmented tangential BDS values by a factor of 1.4 - 1.7 following the decrease of the roughness.
引用
收藏
页码:3047 / 3054
页数:8
相关论文
共 18 条
[1]  
Almqvist A., 2006, THESIS LULEA U TECHN, P31
[2]  
[Anonymous], 2007, IEC 625312007 E, P1, DOI [10.1109/IEEESTD.2007.4288250, DOI 10.1109/IEEESTD.2007.4288250]
[3]  
[Anonymous], IEEE INT S EL INS
[4]  
Chan J. C., 1993, IEEE Electrical Insulation Magazine, V9, P8, DOI 10.1109/57.216782
[5]  
CIGRE J., 2002, ELECTRA, P53
[6]  
Dissado L.A., 1992, Electrical degradation and breakdown in polymers, V9
[7]   Effect of Surface Smoothness on Tracking Mechanism in XLPE-Si-Rubber Interfaces [J].
Du, B. X. ;
Zhu, X. H. ;
Gu, L. ;
Liu, H. J. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2011, 18 (01) :176-181
[8]   Effects of Interfacial Pressure on Tracking Failure between XLPE and Silicon Rubber [J].
Du, B. X. ;
Gu, L. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2010, 17 (06) :1922-1930
[9]  
Fournier D., 1992, Sixth International Conference on Dielectric Materials, Measurements and Applications (Conf. Publ. No.363), P330
[10]  