Data-Driven Online System Equivalent for Self-Adaptive Droop Voltage Control of Wind Power Plants

被引:12
作者
Guo, Yifei [1 ]
Gao, Houlei [1 ]
机构
[1] Shandong Univ, Minist Educ, Key Lab Power Syst Intelligent Dispatch & Control, Jinan 250061, Peoples R China
基金
中国国家自然科学基金;
关键词
Droop control; online system identification; voltage control; wind power plant (WPP);
D O I
10.1109/TEC.2020.2965807
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This letter considers the closed-loop stability issue of droop-based voltage control for wind power plants (WPPs) under varying grid strength. We first propose a data-driven online system equivalent/identification method (DOnSE) for WPPs using the weighted least-squares estimation (WLSE). Then, upon the analysis of link between stability boundary of droop gain and external grid strength, a self-adaptive gain-scheduling droop voltage control scheme for WPPs based on the DOnSE is developed to enhance the closed-loop stability and reactive power utilization of wind turbines (WTs).
引用
收藏
页码:302 / 305
页数:4
相关论文
共 16 条
[1]   Online Tracking of Thevenin Equivalent Parameters Using PMU Measurements [J].
Abdelkader, Sobhy M. ;
Morrow, D. John .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2012, 27 (02) :975-983
[2]  
Alvarez Martin J.A., 2011, 2011 N AM POWER S, P1
[3]  
Asadollash S., IEEE Transactions on Sustainable Energy
[4]   A digital controlled PV-inverter with grid impedance estimation for ENS detection [J].
Asiminoaei, L ;
Teodorescu, R ;
Blaabjerg, F ;
Borup, U .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2005, 20 (06) :1480-1490
[5]  
Berizzi A., 2012, 2012 IEEE International Energy Conference (ENERGYCON 2012), P674, DOI 10.1109/EnergyCon.2012.6348237
[6]   An Optimal Thevenin Equivalent Estimation Method and its Application to the Voltage Stability Analysis of a Wind Hub [J].
Burchett, Stephen M. ;
Douglas, Daniel ;
Ghiocel, Scott G. ;
Liehr, Maximilian W. A. ;
Chow, Joe H. ;
Kosterev, Dmitry ;
Faris, Anthony ;
Heredia, Eric ;
Matthews, Gordon H. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2018, 33 (04) :3644-3652
[7]   Measurement-Based Estimation of Linear Sensitivity Distribution Factors and Applications [J].
Chen, Yu Christine ;
Dominguez-Garcia, Alejandro D. ;
Sauer, Peter W. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2014, 29 (03) :1372-1382
[8]   A real-time voltage instability identification algorithm based on local phasor measurements [J].
Corsi, Sandro ;
Taranto, Glauco N. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2008, 23 (03) :1271-1279
[9]   Distributed cooperative voltage control of wind farms based on consensus protocol [J].
Guo, Yifei ;
Gao, Houlei ;
Wu, Qiuwei .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2019, 104 :593-602
[10]   Centralised power control of wind farm, with doubly fed induction generators [J].
Hansen, AD ;
Sorensen, P ;
Iov, F ;
Blaabjerg, F .
RENEWABLE ENERGY, 2006, 31 (07) :935-951