Performance Evaluation of a Maisotsenko Cycle Cooling Tower with Uneven Length of Dry and Wet Channels in Hot and Humid Conditions

被引:1
作者
Fan, Xuchen [1 ]
Lu, Xiaofeng [1 ]
Wang, Jiping [2 ]
Li, Zilong [2 ]
Wang, Quanhai [1 ]
Dong, Zhonghao [1 ]
Zhang, Rongdi [1 ]
机构
[1] Chongqing Univ, Key Lab Low Grade Energy Utilizat Technol & Syst, Minist Educ China, Chongqing 400044, Peoples R China
[2] State Power Investment Corp SPIC, Yuanda Environm Protect Sci & Technol Branch, Chongqing 400012, Peoples R China
关键词
Maisotsenko cycle; wet cooling tower; wet-bulb effectiveness; parallel counter-flow arrangement fills; THERMAL PERFORMANCE; EXCHANGER; CLIMATE; SYSTEM; WATER; HEAT;
D O I
10.3390/en14248249
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The use of the Maisotsenko cycle (M-Cycle) in traditional wet cooling towers (TWCTs) has the potential to reduce the costs of electricity generation by cooling water below the inlet air's wet-bulb temperature. TWCTs cannot provide sufficient cooling capacity for the increasing demand for cooling energy in the power and industrial sectors-especially in hot and wet climates. Due to this fact, an experimental system of an M-Cycle cooling tower (MCT) with parallel counter-flow arrangement fills was constructed in order to provide perspective on the optimal length of dry channels (l(dry)), thermal performance under different conditions, and pressure drops of the MCT. Results showed that the optimal value of l(dry) was 2.4 m, and the maximum wet-bulb effectiveness was up to 180%. In addition, the impact of air velocity in wet channels on the pressure drops of the novel fills was also summarized. This study confirms the great potential of using the M-Cycle in TWCTs, and provides a guideline for the industrial application and performance improvement of MCTs.
引用
收藏
页数:15
相关论文
共 28 条
  • [2] Comparative evaluation of hybrid (dry/wet) cooling tower performance
    Asvapoositkul, Wanchai
    Kuansathan, Mantheerapol
    APPLIED THERMAL ENGINEERING, 2014, 71 (01) : 83 - 93
  • [3] Performance study of the cross-flow Maisotsenko cycle in humid climate conditions
    Pandelidis, Demis
    Cichon, Aleksandra
    Pacak, Anna
    Drag, Pawel
    Drag, Marlena
    Worek, William
    Cetin, Sabri
    INTERNATIONAL COMMUNICATIONS IN HEAT AND MASS TRANSFER, 2020, 115
  • [4] Hybrid Cooling Tower for a Solar Adsorption Cooling System: Comparative Study Between Dry and Wet Modes in Hot Working Conditions
    Kheireddine, Mohamed-Abdelbassit
    Rouag, Amar
    Benchabane, Adel
    Boutif, Nora
    Labed, Adnane
    ENVIRONMENTALLY-BENIGN ENERGY SOLUTIONS, 2020, : 293 - 308
  • [5] Investigation on the cooling performance of mechanical draft dry-wet hybrid cooling tower
    Zhao, Cuilin
    Wang, Mingwei
    Gao, Qi
    Cheng, Shen
    He, Suoying
    Zhao, Jifang
    Zhan, Jianwei
    Liu, Zhilan
    Geng, Zhe
    Zhang, Shuzhen
    Qi, Jianhui
    Gao, Ming
    Shi, Yuetao
    APPLIED THERMAL ENGINEERING, 2023, 228
  • [6] Neuromuscular Activity during Cycling Performance in Hot/Dry and Hot/Humid Conditions
    Baillot, Michelle
    Hue, Olivier
    Tran, Trong Than
    Antoine-Jonville, Sophie
    LIFE-BASEL, 2021, 11 (11):
  • [7] Experimental performance evaluation of solid concrete and dry insulation materials for passive buildings in hot and humid climatic conditions
    Rehman, Hassam Ur
    APPLIED ENERGY, 2017, 185 : 1585 - 1594
  • [8] AN ANALYTICAL MODEL ON THERMAL PERFORMANCE EVALUATION OF COUNTER FLOW WET COOLING TOWER
    Wang, Qian
    Wang, Pei-Hong
    Su, Zhi-Gang
    THERMAL SCIENCE, 2017, 21 (06): : 2491 - 2501
  • [9] Performance analysis of a desiccant evaporative cooling system under hot and humid conditions
    Rafique, M. Mujahid
    Gandhidasan, P.
    Rehman, Shafiqur
    Alhems, Luai M.
    ENVIRONMENTAL PROGRESS & SUSTAINABLE ENERGY, 2016, 35 (05) : 1476 - 1484
  • [10] Adoption of enclosure and windbreaks to prevent the degradation of the cooling performance for a natural draft dry cooling tower under crosswind conditions
    Wang, Weiliang
    Zhang, Hai
    Li, Zheng
    Lv, Junfu
    Ni, Weidou
    Li, Yongsheng
    ENERGY, 2016, 116 : 1360 - 1369