Effect of a lossy dispersive ground on lightning overvoltages transferred to the low-voltage side of a single-phase distribution transformer

被引:10
作者
De Conti, Alberto [1 ]
Oliveira, Vinicius C. [1 ]
Rodrigues, Phelippe R. [1 ]
Silveira, Fernando H. [1 ]
Silvino, Jose L. [1 ]
Alipio, Rafael [2 ]
机构
[1] UFMG Fed Univ Minas Gerais, LRC, Av Antonio Carlos 6627, BR-31270901 Belo Horizonte, MG, Brazil
[2] CEFET MG Fed Ctr Technol Educ, Dept Elect Engn, Belo Horizonte, MG, Brazil
关键词
Lightning; Frequency-dependent ground parameters; Wideband transformer model; Transferred voltages; Transmission lines; FREQUENCY-DEPENDENCE; OVERHEAD LINES; SOIL; TRANSIENT; REPRESENTATION; PARAMETERS; IMPEDANCE; FORMULA;
D O I
10.1016/j.epsr.2017.01.009
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a study of lightning overvoltages transferred to the low-voltage side of a 10 kVA 7.967 kV/240-120V single-phase distribution transformer considering dispersive ground effects in the medium-voltage distribution line terminated at its primary side. A two-port wideband model that is capable to represent the transformer behavior under different load conditions is considered. The medium voltage distribution line is modeled using Marti's transmission line model modified to include the variation with frequency of the ground resistivity and permittivity. Periodical grounding points are also modeled considering dispersive ground effects. Phase-neutral voltages transferred to the transformer secondary are calculated for direct lightning strikes at the medium-voltage line including insulation breakdown, surge arresters, and different load conditions. It is shown that the frequency variation of the ground resistivity and permittivity can significantly affect voltages transferred to the low-voltage side of the transformer if a high-resistivity soil is considered, depending on load conditions and on flashover occurrence. It is also shown that the importance of considering or neglecting frequency-dependent ground parameters on lightning overvoltages transferred to the secondary side of the transformer is minimized by the installation of a medium-voltage surge arrester at its primary side. (C) 2017 Elsevier B.V. All rights reserved.
引用
收藏
页码:104 / 110
页数:7
相关论文
共 25 条
[1]  
Alipio R., 2014, IEEE T ELECTROMAGN C, V56
[2]   Frequency Dependence of Soil Parameters: Effect on the Lightning Response of Grounding Electrodes [J].
Alipio, Rafael ;
Visacro, Silverio .
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2013, 55 (01) :132-139
[3]  
Anderson R.B., 1980, ELECTRA, V69, P65
[4]   A Comparison of Frequency-Dependent Soil Models: Application to the Analysis of Grounding Systems [J].
Cavka, Damir ;
Mora, Nicolas ;
Rachidi, Farhad .
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2014, 56 (01) :177-187
[5]  
De Conti A., 2015, P INT S LIGHTN PROT
[6]   Analytical representation of single- and double-peaked lightning current waveforms [J].
De Conti, Alberto ;
Visacro, Silverio .
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2007, 49 (02) :448-451
[7]   Revision, extension, and validation of Jordan's formula to calculate the surge impedance of vertical conductors [J].
De Conti, Alberto ;
Visacro, Silverio ;
Soares, Amilton, Jr. ;
Aurelio, Marco .
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2006, 48 (03) :530-536
[8]   Extension of a modal-domain transmission line model to include frequency-dependent ground parameters [J].
De Conti, Alberto ;
Emidio, Maique Paulo S. .
ELECTRIC POWER SYSTEMS RESEARCH, 2016, 138 :120-130
[9]   Calculation of Lightning-Induced Voltages on Overhead Distribution Lines Including Insulation Breakdown [J].
De Conti, Alberto ;
Perez, Ernesto ;
Soto, Edison ;
Silveira, Fernando H. ;
Visacro, Silverio ;
Torres, Horacio .
IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (04) :3078-3084
[10]   Wide band modeling of power transformers [J].
Gustavsen, B .
IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (01) :414-422