Assessing the Impacts of Natural Ventilation on Building Energy Use: A Case Study of a Mid-Rise Residential Building in Chicago, IL

被引:0
作者
Kang, Insung [1 ]
Maristany, Alvaro Diego [1 ]
Acqua, Edoarda Corradi Dell' [1 ]
Stephens, Brent [1 ]
Heidarinejad, Mohammad [1 ]
机构
[1] Illinois Inst Technol, Dept Civil Architectural & Environm Engn, Chicago, IL 60616 USA
来源
ASHRAE TRANSACTIONS 2021, VOL 128, PT 1 | 2022年 / 128卷
关键词
WIND-TUNNEL EXPERIMENTS; CROSS-VENTILATION; CFD SIMULATION; PERFORMANCE; PREDICTION; ROOF;
D O I
暂无
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Natural ventilation as a passive strategy in buildings has been increasingly studied in recent years for its potential advantages to reduce building energy use and improve indoor environmental quality (IEQ), especially during shoulder seasons (i.e., transition months or colder summer days). This study investigates the energy impacts of natural ventilation in a mid-rise multifamily building in Chicago, IL, using computational fluid dynamics (CFD) simulations and building energy modeling. Considering weather conditions in Chicago, natural ventilation is assumed to be applied only for the shoulder seasons (i.e., spring and fall). To this end, this study used (1) a coupled modeling method to simulate the exterior environment to investigate the overall behavior of outdoor airflow around the building, (2) a decoupled modeling method to simulate the detailed interior environment with various opening scenarios to demonstrate natural ventilation effectiveness, (3) applied building energy models to evaluate the impact of natural ventilation on energy use compared to mechanical ventilation, and (4) performed a parametric analysis to explorevarious natural ventilation scenarios with different environmental control set points, including minimum and maximum outdoor temperatures and wind speeds. The CFD simulations showed that the rates of wind-driven natural ventilation were estimated to be about 8430 L/s (25.4 ACH) in the gym space and 1270 to 2050 L/s (4.8 to 7.8 ACH) in the residential space at average shoulder season climate conditions, depending on different ventilation scenarios, which satisfied the required ASHRAE Standard 62.1-2019 minimum ventilation rates. The parametric study of building energy simulations indicated that natural ventilation can reduce seasonal building energy consumption by up to 30% (21,610 kWh) and save about $1550 during the shoulder seasons compared to the mechanical ventilation system.
引用
收藏
页码:550 / 561
页数:12
相关论文
共 35 条
[1]  
[Anonymous], 2017, ASHRAE Handbook-Fundamentals
[2]  
[Anonymous], 2020, Thermal Environmental Conditions for Human Occupancy
[3]  
[Anonymous], 2019, ANSI/ASHRAE Standard 37-2009 (RA 2019). Methods of Testing for Rating Electrically Driven Unitary Air-Conditioning and Heat Pump Equipment, DOI DOI 10.1201/9780849338960.CH6
[4]  
ANSYS, 2019, ANSYS Fluent, CFD Simulation Reference
[5]  
ASHRAE, 2014, ANSI/ASHRAE/USGBC/IES Standard 189.1-2014
[6]   Computational analysis of the performance of a venturi-shaped roof for natural ventilation: Venturi-effect versus wind-blocking effect [J].
Blocken, B. ;
van Hooff, T. ;
Aanen, L. ;
Bronsema, B. .
COMPUTERS & FLUIDS, 2011, 48 (01) :202-213
[9]   Wind tunnel experiments on wind-induced natural ventilation rate in residential basements with areaway space [J].
Bu, Zhen ;
Kato, Shinsuke ;
Takahashi, Takeo .
BUILDING AND ENVIRONMENT, 2010, 45 (10) :2263-2272
[10]  
Burton T, 2001, Wind energy: handbook, DOI 10.1002/0470846062