Quantifying chlorine-reactive substances to establish a chlorine decay model of reclaimed water using chemical chlorine demands

被引:27
|
作者
Wang Yun-Hong [1 ]
Wu Yin-Hu [1 ]
Du Ye [1 ]
Li Qing [1 ]
Cong Yi [1 ]
Huo Zheng-Yang [1 ]
Chen Zhuo [1 ,2 ]
Yang Hong-Wei [1 ]
Liu Shu-Ming [1 ]
Hu Hong-Ying [1 ,2 ]
机构
[1] Tsinghua Univ, Sch Environm, State Environm Protect Key Lab Microorganism Appl, Environm Simulat & Pollut Control State Key Joint, Beijing 100084, Peoples R China
[2] Tsinghua Berkeley Shenzhen Inst, Shenzhen Environm Sci & New Energy Technol Engn L, Shenzhen 518055, Peoples R China
基金
中国国家自然科学基金; 国家重点研发计划;
关键词
Chlorine decay model; Reclaimed water; Chlorine demands; Residual chlorine; DISSOLVED ORGANIC-MATTER; DRINKING-WATER; BULK-DECAY; RECLAMATION; RESIDUALS; KINETICS; REUSE;
D O I
10.1016/j.cej.2018.09.091
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
In order to guarantee the water quality of reclaimed water in pipeline system, a chlorine bulk-decay model is required for simulation and prediction of chlorine profiles in networks. Conventional chlorine decay models of drinking water are not applicable to reclaimed water due to its complex and varying water quality. In this study, the chlorine decay of reclaimed water was investigated under different operational conditions. Based on these results, different chlorine-reactive substances (CRSs) in reclaimed water were quantified by total chlorine demand (TCD), instantaneous chlorine demand (ICD) and lasting chlorine demand (LCD), respectively. A stoichiometric model (CRS model) of chlorine decay of reclaimed water was established using ICD, TCD and reaction rate constant (k) as key independent parameters. The experimental data were fitted to the CRS model with promising results under various initial chlorine concentrations (3-10 mg-Cl-2/L) and temperatures (8-35 degrees C). The ICD, TCD and k of different reclaimed water samples were in the range of 0.23 to 2.85 mg-Cl-2/L, 1.07 to 4.73 mg-Cl-2/L, and 0.04 to 4.06 L/(mg.h), respectively. Furthermore, the ICDs, TCDs and k could be determined directly by measuring the chlorine consumption at 5 min (Delta C-Cl,C-5min) and 8 h (Delta C-Cl,C-8h) after the addition of chlorine into reclaimed water, and the UV254 of reclaimed water, respectively. The relationships between ICD, TCD, k and the corresponding water quality indexes were further validated. In this way, the chlorine decay profile of reclaimed water could be predicted rapidly and precisely by measuring the Delta C-Cl,C-5min, Delta C-Cl,C-8h, and UV254 of reclaimed water.
引用
收藏
页码:791 / 798
页数:8
相关论文
共 27 条
  • [1] Research on Residual Chlorine Decay Model of Reclaimed Water Network
    Chi Haiyan
    Zhao Xinhua
    Yin Yin
    Chi Haiyan
    2011 INTERNATIONAL CONFERENCE ON ELECTRONICS, COMMUNICATIONS AND CONTROL (ICECC), 2011, : 3899 - 3902
  • [2] The Influence of Organic Matter Origin on the Chlorine Bulk Decay Coefficient in Reclaimed Water
    Kang, Sung-Won
    Ahn, Kwang-Ho
    WATER, 2022, 14 (05)
  • [3] General Model of Chlorine Decay in Blends of Surface Waters, Desalinated Water, and Groundwaters
    Fisher, Ian
    Kastl, George
    Sathasivan, Arumugam
    Cook, David
    Seneverathne, Lalantha
    JOURNAL OF ENVIRONMENTAL ENGINEERING, 2015, 141 (12)
  • [4] Modeling Chlorine Decay in Reclaimed Water Distribution Systems-A Lisbon Area Case Study
    Costa, Joana
    Mesquita, Elsa
    Ferreira, Filipa
    Figueiredo, David
    Rosa, Maria Joao
    Viegas, Rui M. C.
    SUSTAINABILITY, 2023, 15 (23)
  • [5] A variable reaction rate model for chlorine decay in drinking water due to the reaction with dissolved organic matter
    Hua, Pei
    Vasyukoua, Ekaterina
    Uhl, Wolfgang
    WATER RESEARCH, 2015, 75 : 109 - 122
  • [6] A variable parabolic reaction coefficient model for chlorine decay in bulk water
    Zhong, Dan
    Feng, Weinan
    Ma, Wencheng
    Ma, Jun
    Du, Xuan
    Zhou, Ziyi
    WATER RESEARCH, 2021, 201
  • [7] A comprehensive bulk chlorine decay model for simulating residuals in water distribution systems
    Fisher, Ian
    Kastl, George
    Sathasivan, Arumugam
    URBAN WATER JOURNAL, 2017, 14 (04) : 361 - 368
  • [8] A study on evaluation of the pipe wall decay constants of residual chlorine and affecting factors in reclaimed water supply system
    Lee, H. D.
    Park, J. H.
    Kang, S. W.
    Kong, M. S.
    DESALINATION AND WATER TREATMENT, 2015, 53 (09) : 2378 - 2387
  • [9] A Mathematical Model for Variable Chlorine Decay Rates in Water Distribution Systems
    Tiruneh, Ababu T.
    Debessai, Tesfamariam Y.
    Bwembya, Gabriel C.
    Nkambule, Stanley J.
    MODELLING AND SIMULATION IN ENGINEERING, 2019, 2019
  • [10] Chlorine decay prediction in bulk water using the parallel second order model: An analytical solution development
    Kohpaei, Ahmad Jabari
    Sathasivan, Arumugam
    CHEMICAL ENGINEERING JOURNAL, 2011, 171 (01) : 232 - 241