Observational and Experimental Study of the Lightning Stroke Attraction Effect with Ground Wire System Constructions

被引:9
作者
Oguchi, Shuichi [1 ]
Ishii, Tsunayoshi [1 ]
Okabe, Shigemitsu [1 ]
Sakamoto, Yoshiki [1 ]
Tsuji, Masaki [1 ]
Asakawa, Akira [2 ]
机构
[1] Tokyo Elect Power Co Ltd, Tsurumi Ku, Yokohama, Kanagawa 2308510, Japan
[2] Cent Res Inst Elect Power Ind, Yokosuka, Kanagawa 2400196, Japan
关键词
Lightning stroke; ground wire (GW); GW cap; lightning protection; lightning shielding; CONDUCTORS;
D O I
10.1109/TDEI.2012.6148539
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Although power distribution lines are protected by ground wire systems, there are fears that these ground wires may break at their corrosion points. For practical purposes, they have therefore been removed to avoid maintenance in certain areas. The Tokyo Electric Power Company (TEPCO) has continuously observed lightning strokes and obtained 321 datasets to date. The present study has determined the potential for an anticipated lightning stroke attraction effect based on the observed data, despite the fact ground wires are eliminated while ground wire caps are left in place. Furthermore, a verification experiment using facilities simulating the power distribution system has confirmed the problem of insulated wires being struck by lightning and the extent of the impact of the ground wire cap on the lightning stroke attraction effect. These results are expected to provide a new facility-construction menu, which will help rationalize the lightning protection design.
引用
收藏
页码:363 / 370
页数:8
相关论文
共 15 条
[1]  
[Anonymous], 1985, IEEE T POWER AP SYST, V104, P919
[2]  
[Anonymous], 1995, T40 CRIEPI LIGHTN PR
[3]  
[Anonymous], 2002, T69 CRIEPI LIGHTN PR
[4]  
Barker P., 1993, IEEE Power Engineering Review, V13, P23, DOI 10.1109/39.214979
[5]  
Hashimoto Y., 1995, T IEEJ JAPAN B, V115-B, P1508
[6]   Discussion on measures against lightning breakage of covered conductors on distribution lines [J].
He, Jinliang ;
Gu, Shanqiang ;
Chen, Shuiming ;
Zeng, Rong ;
Chen, Weijiang .
IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (02) :693-702
[7]  
IEEE, 2004, IEEE Std 1410-2004
[8]   An experimental validation of lightning performance in distribution lines [J].
Miyazaki, Teru ;
Okabe, Shigemitsu ;
Sekioka, Shozo .
IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (04) :2182-2190
[9]   A Detailed Field Study of Lightning Stroke Effects on Distribution Lines [J].
Miyazaki, Teru ;
Okabe, Shigemitsu .
IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (01) :352-359
[10]   Mitigation of lightning-induced overvoltages in medium voltage distribution lines by means of periodical grounding of shielding wires and of surge arresters: Modeling and experimental validation [J].
Paolone, M ;
Nucci, CA ;
Petrache, E ;
Rachidi, F .
IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (01) :423-431