Preliminary sanitary analysis of supply and exhaust air of ventilation units working at special rooms

被引:3
作者
Szczesniak, Sylwia [1 ]
Trusz-Zdybek, Agnieszka [1 ]
Piekarska, Katarzyna [1 ]
机构
[1] Wroclaw Univ Technol, Wydzial Inzynierii Srodowiska, Wyb Wyspianskiego 27, PL-50370 Wroclaw, Poland
来源
INTERNATIONAL CONFERENCE ON ADVANCES IN ENERGY SYSTEMS AND ENVIRONMENTAL ENGINEERING (ASEE17) | 2017年 / 22卷
关键词
D O I
10.1051/e3sconf/20172200171
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This article is an attempt to estimate concentration of bacteria and fungi in characteristic places in two air handling units. The research was conducted with the units equipped with heat recovery exchanger and recirculation of exhaust air. Additionally, microbiological analysis was done for indoor and fresh air. We performed measurements regarding supply and exhaust air volume. This means that the air velocity inside ventilator chamber was known. The mean concentration of bacteria and fungi was specified for air filters on the supply and exhaust side. The efficiency of air filters was verified by the concertation of bacteria and fungi in fan chamber. This article confirms that bacteria content in supply air is always lower than in exhaust air despite air recirculation. In this work we proved that the position of Petrie plate is essential for bacteria and fungi measurement.
引用
收藏
页数:8
相关论文
共 7 条
[1]  
Awbi H.B., 2003, Ventilation of Buildings
[2]  
Bródka K, 2012, MED PR, V63, P303
[3]  
Flannigan B, 2011, MICROORGANISMS IN HOME AND INDOOR WORK ENVIRONMENTS: DIVERSITY, HEALTH IMPACTS, INVESTIGATION AND CONTROL, 2ND EDITION
[4]   Study on some factors affecting survivability of airborne fungi [J].
Hameed, A. A. Abdel ;
Khoder, M. I. ;
Ibrahim, Y. H. ;
Saeed, Y. ;
Osman, M. E. ;
Ghanem, S. .
SCIENCE OF THE TOTAL ENVIRONMENT, 2012, 414 :696-700
[5]  
Kiliszczyk A., 2013, Woda Srodowisko Obszary Wiejskie, V13, P79
[6]  
Pelech A, 2009, WENTYLACJA KLIMATYZA
[7]  
Przydrozny S., 1991, WENTYLACJA