Performance analysis of a solar-driven liquid desiccant cooling system with solution storage under adjustable recirculation ratio

被引:25
|
作者
Zhang, Fan [1 ]
Yin, Yonggao [1 ,2 ]
Zhang, Xiaosong [1 ,2 ]
机构
[1] Southeast Univ, Sch Energy & Environm, Nanjing 210096, Jiangsu, Peoples R China
[2] Southeast Univ, Jiangsu Prov Key Lab Solar Energy Sci & Technol, Nanjing 210096, Jiangsu, Peoples R China
基金
国家重点研发计划;
关键词
Dehumidification; Evaporative cooling; Liquid desiccant; Solar cooling; Energy storage; ABSORPTION-REFRIGERATION SYSTEM; AIR-CONDITIONING SYSTEMS; MASS-TRANSFER; ENERGY-CONSUMPTION; THEORETICAL-ANALYSIS; DYNAMIC SIMULATION; DEHUMIDIFICATION; WATER; STRATEGIES; EXCHANGER;
D O I
10.1016/j.solener.2018.03.061
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Solar cooling is one of the most promising solutions to the worsening energy and climate issues. A solar-driven liquid desiccant evaporative cooling air-conditioning system with solution storage tanks was proposed. The daily performance of the proposed system under the variable solution recirculation ratio (R-s) adjusting method in a typical hot-humid summer day of Nanjing was investigated using a quasi-dynamic mathematical model. The solution storage effect and the coupled characteristics of the solar collecting subsystem and the liquid desiccant cycle were taken into account. The effects of water tank volume (V-wt), the initial solution mass in the solution storage tank (M-s(,storage,tank)) and the area of solar collector (A(sc)) on the overall system performance were also evaluated. The results show that with the help of the stored solution, the proposed system can effectively handle the space cooling load during the whole period of operation. The average values of thermal coefficient of performance (TCOP) and solar coefficient of performance (SCOP) are 0.66 and 0.31, respectively. The variable R-s adjusting method can guarantee the required solution concentration and adapt well to the varying solar radiation. When A(sc) is limited, a smaller V-wt and a larger M-s(,storage,tank) are recommended to achieve a higher SCOP when covering the required space cooling load.
引用
收藏
页码:32 / 45
页数:14
相关论文
共 50 条
  • [31] Performance optimization and multi-objective analysis of an innovative solar-driven combined power and cooling system
    Yadav, Vinay Kumar
    Sarkar, Jahar
    Ghosh, Pradyumna
    ENERGY AND BUILDINGS, 2024, 307
  • [32] Energetic performance analysis of a solar-driven hybrid ejector cooling and humidification-dehumidification desalination system
    Almahmoud, Hamad A.
    Al-Sulaiman, Fahad A.
    Ibrahim, Nasiru I.
    Ben Mansour, Ridha
    Alkhulai, Yousif M.
    ENERGY, 2021, 230
  • [33] Parameter analysis and optimization of the energy and economic performance of solar-assisted liquid desiccant cooling system under different climate conditions
    Qi Ronghui
    Lu Lin
    Huang Yu
    ENERGY CONVERSION AND MANAGEMENT, 2015, 106 : 1387 - 1395
  • [34] A hybrid solar-driven membrane distillation-assisted liquid desiccant air conditioning system: Mathematical modeling and feasibility analysis
    Liu, Jingjing
    Lin, Wenye
    Hai, Faisal I.
    Ma, Zhenjun
    ENERGY CONVERSION AND MANAGEMENT, 2024, 314
  • [35] Selection of optimal mixed liquid desiccants and performance analysis of the liquid desiccant cooling system
    Zhao, Xiao
    Li, Xiuwei
    Zhang, Xiaosong
    APPLIED THERMAL ENGINEERING, 2016, 94 : 622 - 634
  • [36] PERFORMANCE ANALYSIS OF AN OPEN-CYCLE LIQUID DESICCANT COOLING SYSTEM USING SOLAR-ENERGY FOR REGENERATION
    GANDHIDASAN, P
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1994, 17 (07): : 475 - 480
  • [37] Enhancing indoor thermal comfort and sustainability: A solar-driven desiccant cooling and adsorption chiller system with environmental impact assessment
    Bozorgi, Mehran
    Tasnim, Syeda Humaira
    Mahmud, Shohel
    SOLAR ENERGY, 2024, 271
  • [38] Study of a solar-driven membrane distillation system: Evaporative cooling effect on performance enhancement
    Kabeel, A. E.
    Abdelgaied, Mohamed
    El-Said, Emad M. S.
    RENEWABLE ENERGY, 2017, 106 : 192 - 200
  • [39] THERMODYNAMIC ANALYSIS OF A LIQUID DESICCANT COOLING SYSTEM UNDER MEDITERRANEAN CLIMATIC CONDITIONS
    Koronaki, I. P.
    Christodoulaki, R. I.
    Papaefthimiou, V. D.
    Rogdakis, E. D.
    INTERNATIONAL MECHANICAL ENGINEERING CONGRESS AND EXPOSITION - 2012, VOL 6, PTS A AND B, 2013, : 137 - 146
  • [40] Research on Ratio Selection of Mixed LiBr-CaCl2 Solution for Liquid Desiccant Cooling System
    Zhao, Xiao
    Li, Xiuwei
    Wang, Fang
    Development of Industrial Manufacturing, 2014, 525 : 598 - 602