Experimental study of intermittent spray cooling on suppression for lithium iron phosphate battery fires

被引:71
作者
Meng, Xiangdong [1 ]
Li, Shi [2 ]
Fu, Weidong [2 ]
Chen, Yuwei [2 ]
Duan, Qiangling [1 ]
Wang, Qingsong [1 ]
机构
[1] Univ Sci & Technol China, State Key Lab Fire Sci, Hefei 230026, Peoples R China
[2] Zhengzhou Slanpower Technol Co Ltd, Zhengzhou 450000, Peoples R China
基金
中国国家自然科学基金;
关键词
Lithium ion battery safety; Thermal runaway; C6F12O; Intermittent spray cooling; Fire suppression; ION BATTERIES; BOILING REGIMES; SINGLE-PHASE; BEHAVIOR; EFFICIENCY;
D O I
10.1016/j.etran.2021.100142
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Nowadays, fires caused by thermal runaway (TR) of lithium ion battery (LIB) remains a potential risk in its application. An effective method is urgently required to suppress LIB fires. In this work, a novel cooling method combining dodecafluoro-2-methylpentan-3-one (C6F12O) agent with intermittent spray cooling (ISC) is proposed for suppression of lithium iron phosphate (LFP) battery fires. Besides, the influence of spray frequency and duty cycle (DC) on spray cooling efficiency are discussed. The results indicate that atomized C6F12O can effectively suppress LFP fires, reduce the production of toxic gases and heat release rate (HRR). However, after C6F12O runs out, the rapidly elevated temperature and the release of combustible gases mean that the TR battery requires longer and more efficient cooling. Compared with continuous spray cooling (CSC), ISC not only extends low temperature duration but also decreases the temperature rise rate of the battery. As DC increasing, C6F12O agent first exhibits an enhancement effect and then an inhibition effect on cooling performance. It is suggested that the optimum DC is 55.4% for the suppression of 14 Ah LFP fires. For the LIBs with higher capacity and higher fraction of active materials, the optimum DC is required to be higher. (C) 2021 Elsevier B.V. All rights reserved.
引用
收藏
页数:15
相关论文
共 48 条
[1]   Safety focused modeling of lithium-ion batteries: A review [J].
Abada, S. ;
Marlair, G. ;
Lecocq, A. ;
Petit, M. ;
Sauvant-Moynot, V. ;
Huet, F. .
JOURNAL OF POWER SOURCES, 2016, 306 :178-192
[2]  
Alex Prilutsky, 2015, ACTIVE THERMAL RUNAW
[3]   A Review on Temperature-Dependent Electrochemical Properties, Aging, and Performance of Lithium-Ion Cells [J].
Alipour, Mohammad ;
Ziebert, Carlos ;
Conte, Fiorentino Valerio ;
Kizilel, Riza .
BATTERIES-BASEL, 2020, 6 (03) :1-32
[4]   New concept of surface modification to LiCoO2 [J].
Bai, Ying ;
Yin, Yanfeng ;
Liu, Na ;
Guo, Bingkun ;
Shi, Hongjun ;
Liu, Jianyong ;
Wang, Zhaoxiang ;
Chen, Liquan .
JOURNAL OF POWER SOURCES, 2007, 174 (01) :328-334
[5]  
Bergman T.L., 2017, Fundamentals of Heat and Mass Transfer, V8th ed.
[6]   Role of water temperature in case of high mass flux spray cooling of a hot AISI 304 steel plate at different initial surface temperatures [J].
Bhatt, N. H. ;
Chouhan, D. ;
Pati, A. R. ;
Varshney, P. ;
Das, Lily ;
Kumar, A. ;
Munshi, B. ;
Behera, A. ;
Mohapatra, Soumya S. .
EXPERIMENTAL HEAT TRANSFER, 2017, 30 (05) :369-392
[7]   Future Earth and Sustainable Developments [J].
Cheng, Hai .
INNOVATION, 2020, 1 (03)
[8]  
Feng X., 2016, Thermal Runaway Initiation and Propagation of Lithium-Ion Traction Battery for Electric Vehicle: Test, Modeling and Prevention
[9]   Identification and quantification of gases emitted during abuse tests by overcharge of a commercial Li-ion battery [J].
Fernandes, Y. ;
Bry, A. ;
de Persis, S. .
JOURNAL OF POWER SOURCES, 2018, 389 :106-119
[10]   Thermal behaviour of the lithiated-graphite/electrolyte interface through GC/MS analysis [J].
Gachot, Gregory ;
Grugeon, Sylvie ;
Eshetu, Gebrekidan Gebresilassie ;
Mathiron, David ;
Ribiere, Perrine ;
Armand, Michel ;
Laruelle, Stephane .
ELECTROCHIMICA ACTA, 2012, 83 :402-409