Going below the wet-bulb temperature by indirect evaporative cooling: Analysis using a modified ε-NTU method

被引:174
作者
Hasan, Ala [1 ]
机构
[1] Aalto Univ, Sch Engn, Dept Energy Technol, FI-00076 Aalto, Finland
基金
芬兰科学院;
关键词
Indirect evaporative cooling; Effectiveness-NTU method; Sub-wet bulb temperature; SURFACE HEAT-EXCHANGERS;
D O I
10.1016/j.apenergy.2011.07.005
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The objective of this paper is to study a method to achieve sub-wet bulb temperature by indirect evaporative cooling of air (without using a vapor compression machine). For this purpose, an analytical model is developed based on the effectiveness-NTU method (epsilon-NTU). The main idea for achieving a sub-wet bulb temperature by indirect evaporative cooling of air is by indirectly pre-cooling the working air before it enters the wet passage. It is shown that a modified analytical model for indirect evaporative coolers could be based on the epsilon-NTU method for sensible heat exchangers when proper adjustments are made by redefining the potential gradients, transfer coefficient, heat capacity rate parameters and assuming a linear saturation temperature-enthalpy relation of air. This modified model is used to find the performance of a regenerative indirect evaporative cooler. The model results show very good agreement with results from experimental measurements and a numerical model. (C) 2011 Elsevier Ltd. All rights reserved.
引用
收藏
页码:237 / 245
页数:9
相关论文
共 21 条
[1]  
Boxem G., 2007, P CLIM 2007 WELLBEIN
[2]  
Braun J.E., 1989, ASHRAE Transactions, V95, P164
[3]   Thermodynamic performance assessment of a novel air cooling cycle: Maisotsenko cycle [J].
Caliskan, Hakan ;
Hepbasli, Arif ;
Dincer, Ibrahim ;
Maisotsenko, Valeriy .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2011, 34 (04) :980-990
[4]  
Crum DR, 1987, ASHRAE T, V93, P1261
[5]   Performance analysis of two-stage evaporative coolers [J].
El-Dessouky, H ;
Ettouney, H ;
Al-Zeefari, A .
CHEMICAL ENGINEERING JOURNAL, 2004, 102 (03) :255-266
[6]   A modified analysis of counter flow wet cooling towers [J].
ElDessouky, HTA ;
AlHaddad, A ;
AlJuwayhel, F .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1997, 119 (03) :617-626
[7]  
Gillan L., 2008, CLEAN AIR INT J ENER, V9, P47
[8]   Indirect evaporative cooling of air to a sub-wet bulb temperature [J].
Hasan, Ala .
APPLIED THERMAL ENGINEERING, 2010, 30 (16) :2460-2468
[9]   OPTIMIZATION OF WET-SURFACE HEAT-EXCHANGERS [J].
HSU, ST ;
LAVAN, Z ;
WOREK, WM .
ENERGY, 1989, 14 (11) :757-770
[10]  
Incropera F.P., 1990, FUNDAMENTALS HEAT MA