Acoustically Enhanced Water Mist Suppression of Heptane Fueled Flames

被引:13
作者
Friedman, Adam N. [1 ,2 ]
Danis, Peter I. [2 ]
Fiola, Gregory J. [2 ]
Barnes, Christopher A. [2 ]
Stoliarov, Stanislav I. [2 ]
机构
[1] Jensen Hughes, Baltimore, MD 21227 USA
[2] Univ Maryland, Dept Fire Protect Engn, College Pk, MD 20742 USA
关键词
Fire suppression; Acoustics; Water mist; Ceramic fiber wicks; Heptane fueled flame; EXTINGUISHMENT; EXTINCTION;
D O I
10.1007/s10694-018-0777-0
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Recent research has shown that acoustics can be used to suppress flames from a liquid fuel source. The results of these experiments indicated that acoustics alone are insufficient to control flames beyond the incipient stage. Recent research has also shown that variations in the delivery of water mist to a fire can enhance the mist's efficiency. Therefore, the addition of acoustics to water mist may be an effective means of enhancing an established fire protection technology. For the first time, acoustics and water mist have been combined and studied as a flame suppression strategy. A series of experiments were conducted that explored the potential for coupling acoustics with water mist as means of flame suppression. Heptane fueled flames were created from two different sized ceramic fiber wicks: 30mmx50mm with 5mL of fuel, and 60mmx100mm with 20mL of fuel. The flames were then exposed to water mist delivered at a constant rate, which was found to be incapable of suppressing the flames. Next, low frequency sound waves at 62Hz and 80Hz were used to suppress flames from both wicks, with each frequency being generated by a different resonator. Finally, acoustics from both resonators were combined with water mist, and used to suppress flames from both wicks. The results showed that a combination of acoustic waves and water mist suppressed the flames more effectively than each individual technique on its own. This finding opens the possibility of developing more efficient ways to use water mist technology.
引用
收藏
页码:1829 / 1840
页数:12
相关论文
共 24 条
  • [1] [Anonymous], 1994, FIRE SAF SCI
  • [2] Braidech M., 1955, The Mechanism of Extinguishment of Fire by Finely Divided Water: An Investigation
  • [3] Extinguishment of counter-flow diffusion flame by water mist derived from aqueous solutions containing chemical additives
    Feng, Ming-Hui
    Tao, Jun-Jun
    Qin, Jun
    Fei, Qin
    [J]. JOURNAL OF FIRE SCIENCES, 2016, 34 (01) : 51 - 68
  • [4] Acoustic extinction of laminar line-flames
    Friedman, Adam N.
    Stoliarov, Stanislav I.
    [J]. FIRE SAFETY JOURNAL, 2017, 93 : 102 - 113
  • [5] Friedman AN, 2016, THESIS
  • [6] Gagnon R.M., 2008, Design of Special Hazard and Fire Alarm Systems, Vsecond
  • [7] Fire suppression by water sprays
    Grant, G
    Brenton, J
    Drysdale, D
    [J]. PROGRESS IN ENERGY AND COMBUSTION SCIENCE, 2000, 26 (02) : 79 - 130
  • [8] An experimental study of the effects of water mist characteristics on pool fire suppression
    Gupta, Meenakshi
    Pasi, Amit
    Ray, Anjan
    Kale, S. R.
    [J]. EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2013, 44 : 768 - 778
  • [9] Dynamics of water droplets in a counterflow field and their effect on flame extinction
    Lentati, AM
    Chelliah, HK
    [J]. COMBUSTION AND FLAME, 1998, 115 (1-2) : 158 - 179
  • [10] Experimental study of the effect of water mist on CH4/air non-premixed flames
    Liu, Jianghong
    Liao, Guangxuan
    [J]. ISMSSE 2011, 2011, 26